Figure 12c. A wiring example for controlling a proportional valve (0-10Vdc or 2-
10Vdc). One 500 Ohms resistor is required (not included).    

 

b. Parameter settings. Set 

inty

 = P100, 

outy

 = 1, 

coty

 = 0-20 mA or 4-20 mA 

depending on your valve, 

rd

 = 1 (cooling mode), 

SV

 = 50° F, 

AH1

 = 54° F, and 

ot

 

= 2 for fast response. Adjust 

Hy

 (hysteresis band) accordingly. If the input of your 

valve is 0-20 mA, 0-5 Vdc or 0-10 Vdc, please set 

coty = 0 - 20 mA

.

 

If the input of 

your valve is 4-20 mA, 1-5 Vdc or 2-10 Vdc, please set 

coty = 4 - 20 mA

 

11. Error Message and Trouble Shooting

 

11.1 Display EEEE 

This  is  an  input  error  message.  The  possible  reasons  are,  the  sensor  is  not 
connected correctly; the input setting is wrong type; or the sensor is defective. If 
this happens when using thermocouple sensor, you can short terminal 9 and 10 
with a copper wire or paper clip. If then the display shows ambient temperature, 
the thermocouple is probably defective. If this happens when using the RTD sensor, 
check  the  input  sensor  type  (

Inty

)  setting  first  because  most  controllers  are 

shipped with input sensor type set for type K thermocouple. Then check the wiring. 
The two red wires should be on terminal 9 and 10. The clear wire should be on 
terminal 8.  

 
11.2 No output 

When 

outy

 is set to 1 or 2, the control output is sent to the mA port (pin 6 and 7). 

The control output is synchronized with the OUT indicator. The flashing frequency 
of the OUT light is an indication of how much mA current is being sent out. When 

outy

 is set to 3 or 4, the control output is sent through J1 relay. The J1 relay action 

is synchronized with the AL1 indicator. When AL1 is on, J1 relay should pull in; 
when AL1 is off, J1 relay should drop out. If the control signal and the indicator are 
synchronized, please check whether the external device is working properly. 
 

11.3 Poor accuracy

 

Please make sure calibration is done by immersing the probe in liquid. Comparing 
the probe reading with a reference probe in air is not recommended because the 
response time of probes can vary a lot. Different probes are designed for different 
applications, and they can be quite different in their thermal mass, which will affect 
their response time a lot. Some of our sensors have response time more than 10 
minutes in the air. When the calibration is done correctly in liquid and the error is 
5° F or larger, the most common problem for a thermocouple probe is improper 
connection between the thermocouple and the controller. A thermocouple needs 
to  be  connected  directly  to  the  controller  unless  thermocouple  connector  and 
thermocouple  extension  wire  are  used.  A  copper  connector,  copper  wire,  or 
thermocouple extension wire with wrong polarity connected on the thermocouple 
will cause the reading drift more than 5° F. 
 
 
 
 
 

Auber Instruments Inc. 

5755 North Point Parkway, Suite 99, 

Alpharetta, GA 30022 

www.auberins.com 

Email: [email protected] 

Tel: 770-569-8420 

 

Copyright ©  2021 Auber Instruments Inc. All rights reserved. 

No part of this datasheet shall be copied, reproduced, or transmitted in any way without the 

prior, written consent of Auber Instruments. Auber Instruments retains the exclusive rights 

to all information included in this document. 

Summary of Contents for SYL-2381-mA

Page 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Page 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Page 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Page 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Page 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Page 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Page 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Reviews: