6. Auto-tuning

 

 

The Auto-tuning function (also called self-tuning) can automatically optimize the 
PID  parameters  for  the  system.  The  auto-tuning  function  will  provide 

ON/OFF 

mode

 (see 6.3 below for details) to heat up the system until it passes the set point, 

then let it cool down. It will repeat this about three times. Based on the response 
time of the system, the built-in artificial intelligence program will calculate and set 
the PID parameters for the controller. If your system has a very slow response, the 
auto-tuning could take a long time. 
 

AT start

AT calculation

AT end

ON OFF

ON OFF

ON/OFF

PID 

SV

PV

 

 

Figure 8. Auto-tuning. 

 

6.1 

To  start  auto-tuning,  press  and  hold  >  key  about  3  seconds 

until  the  “AT” 

indicator  starts  to  blink,  which  indicates  auto-

tuning  is  in  progress.  When  “AT” 

stops  blinking,  the  auto-tuning  is  finished.  Now,  the  newly  calculated  PID 
parameters are set to be used for the system. Please note that auto-tuning is only 

for PID control mode (when “outy”

 is set at 1, 2 or 3). 

6.2 

To  stop  the  Auto-tuning,  press  and  hold  >  key  about  3  seconds 

until  “AT” 

indicator stops blinking. In this case, no new PID parameters are calculated. The 
control will resume PID control with previous PID parameters.  

6.3

 In SYL-2381-mA. auto-tune can be used for J1 relay as main output modes 

(OUTY = 3 or 4) and linear output as main output modes (OUTY = 1 or 2). When 
you run auto-tune with linear output heating modes (OUTY = 1 or 2, RD = 0), the 
linear output will be either 100% (when your PV is below your SV) or 0% (when 
your PV is over your SV). 
 
 

7. On/off control mode  

In on/off control mode, the controller works like a mechanical thermostat. It simply 

turns on or off the output when PV is below or above the SV. On/off control is not 
as  precise  as  PID  control  mode.  However,  this  control  mode  is  suitable  for 
inductive loads such as motors, compressors, or solenoid valves that do not like 
pulsed power.  

 
When the temperature passes the set point, the heater (or cooler) will be turned 

off. When the temperature drops back to below the hysteresis band (

Hy

) the heater 

will be turned on again. Please see the Note 4 in 5.1 for details.  

 

On this controller, only J1 relay can be used for on/off control. To use the on/off 
mode, set 

outy

 = 4. Then set 

Hy

 to a desired value based on the requirements of 

the control precision. Smaller 

Hy

 values result in tighter temperature control, but 

also cause the on/off action to occur more frequently. In the PID parameters menu 
(code 0036), only 

ot

 and 

FILt

 settings will apply to on/off control mode. Settings 

for other parameters 

P

I

D

, and 

SouF

 have no effect on/off control. 

 

 

Figure 9. On/off control mode for heating (left) and cooling (right), in both 

situations SV = 100 and Hy = 20.  

8. Manual mode

 

Manual mode allows the user to manually adjust the output as a percentage of the 
total  output  power.  It  is  like  a  stove  dial.  The  output  is  independent  of  the 
temperature sensor reading. The manual control mode can only be switched from 
PID control mode, not from on/off control mode. To switch from the PID mode to 
manual mode, press and hold the SET key 4 seconds till the 

AT

 indicator turns 

on. In manual mode, the SV window will show the percentage of the power output. 
The very left digit in the SV window should show letter M 

(

M

)

. To switch from 

manual  mode  to  PID  mode,  press  and  hold  SET  key  4  seconds  till  the 

AT

 

indicator  turns  off.  This  controller  offers 

bumpless

  switch  from  PID  mode  to 

manual mode. For example, if the controller is sending 75% of power in PID mode, 

when user switch to manual mode the controller will show “

m 75

” in the bottom 

display, the output will stay at 75% till the user changes the output percentage. 
 
 

9. Serial communication 

RS485 serial communication is an optional feature available on SYL-2381-mA-S. 
It complies with the widely-accepted MODBUS_RTU protocol. Please refer to the 
supplementary manual for details.  
 
 

10. Application Examples  

10.1 

A furnace needs to be controlled at 1200° F. The power source is 120 V AC. 

The heating element is 1800 W at 120 V. It is switched on/off by a contactor. The 
coil voltage of the contactor is  120  V AC. The temperature sensor is a  type  K 
thermocouple. 
 
a. Wiring diagram. 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

+ -

K type TC

L

N

Fuse

Contactor

Heater

120VAC

 

Figure 10. A typical wiring set up for powder coating oven and kiln. This diagram 
also applies to 240 V AC power system if both the heater and the coil voltage of 
the contactor are 240 V AC. 
 

Summary of Contents for SYL-2381-mA

Page 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Page 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Page 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Page 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Page 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Page 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Page 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Reviews: