SYL-2381-mA PID TEMPERATURE CONTROLLER  

INSTRUCTION MANUAL  

Version 1.3 (May, 2021) 

 

 

Caution 

 

This  controller  is  intended  to  control  equipment  under  normal  operating 
conditions. If failure or malfunction of it could lead to an abnormal operating 
condition that could cause personal injury or damage to the equipment or other 
property,  other  devices  (limit  or  safety  controls)  or  systems  (alarm  or 
supervisory) intended to warn of or protect against failure or malfunction of the 
controller  must  be  incorporated  into  and  maintained  as  part  of  the  control 
system. 

 

Installing the rubber gasket supplied will protect the controller front panel from 
dust and water splash (IP54 rating). Additional protection is needed for higher 
IP rating. 

 

This  controller  carries  a  90-day  warranty.  This  warranty  is  limited  to  the 
controller only. 

 

1. Features 

 

The PID control with artificial intelligent enhancement for precision temperature 
control.  

 

Auto-tuning function can find the best PID parameter automatically.  

 

ON/OFF  control  mode  for  refrigerator,  motor  and  solenoid  valve  control 
application. 

 

Linear output control 0 ~ 20 mA or 4 ~ 20 mA. 

 

Bumpless transfer between Auto and Manual control mode. 

 

Optional serial communication port (RS-485/Modbus_RTU). 

 

The output can be set for linear output controller or relay contactor control by 
the user.  

 

Support 10 different types of commonly used temperature sensor inputs. 

 
2. Specifications 

Input type 

Thermocouple (TC): K, E, S, R, J, T, B, WRe3/25 
RTD (Resistance temperature detector): Pt100, Cu50 

Input range 

See Table 2 

Display 

Dual lines, four digits, ° F or ° C 

Display resolution 

1° C, 1° F; or 0.1° C, 0.1° F with Pt100 

Accuracy 

±  0.2% or ±  1 unit of full input range 

Control mode 

PID, manual 

Output mode 

Relay contact: 3 A at 240 VAC.  
Linear current output: 0 ~ 20 mA, 4 ~ 20 mA. 

Alarm 

Process high/low alarm 

Power 
consumption 

< 2 Watt 

Power supply 

85 ~ 260 VAC / 50 ~ 60 Hz or 85 ~ 260 VDC 

Communication 
(optional) 

RS-485 (Modbus_RTU) 

Operating 
condition 

0 ~ 50° C, 

 

85% RH 

Mounting cutout 

45 x 45 mm 

Dimension 

48 x 48 x 82 mm (1/16 DIN) 

 

3. Front Panel and Operation 

1

2

3

4

5

7

6

 

Figure 1. Front panel

 

 

 AL1: Relay J1 output indicator. 

      AT: ON for manual mode. Blinking during auto-tuning process.  
      OUT: main output indicator. 

 Up key: value increment / select the next parameter. 

 Down key: value decrement / select previous parameter. 

 Shift key: start auto tuning / shift digit / check output percentage* 

 Set key: confirm change / switch between Manual and Auto mode. 

 PV window: measured temperature, or, Process Value (PV)  

 SV window: set temperature, or, Set Value (SV) 

 
Note *: Press Shift key momentarily to change the SV window from set 
temperature to real-time output percentage. It will be 

display as “

o

X

XX”. 

For 

example, 

o 90

” means 

the current output percentage is 90%. Press Shift key 

again to switch back to set temperature.  
 
 

4. Terminal Wiring (back view)

 

 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

+

-

mA

J1

+ -

RTD

TC

           

Po wer

                   

AC/DC

           85-260V

R

R

W

(O

ptio

na

l) 

RS

48

5

A+

B-

 

 

Figure 2. Terminal assignment of SYL-2381-mA. 

 

Instruction Manual

 

 

Summary of Contents for SYL-2381-mA

Page 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Page 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Page 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Page 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Page 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Page 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Page 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Reviews: