b. Parameter settings. These are the parameters that need to be changed from 
the  initial  value: 

outy

  =  3  for  PID  mode  with  J1  relay  output; 

ot

  =  20  to  avoid 

switching the contactor too often; for target temperature set 

SV

 = 1200° F. 

 

10.2 

A 24 V AC solenoid valve is controlled by J1 relay in on/off mode. The valve 

should be on till the temperature reaches 200° F; once the temperature is above 
200° F, it should be shut off. When the temperature drops below 195° F, it should 
be turned on again. The power source is 120 V AC. The temperature sensor is a 
type K thermocouple.  
a. Wiring diagram. 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

+ -

K type TC

L

N

S

Solenoid valve

24VAC

120VAC

Fuse

 

Figure 11. A typical wiring set up for a 24 V AC gas valve, hot water valve, or a 
contactor with 24 V AC coil voltage 
 
b. Parameter settings. These are the parameters that need to be changed from 
the initial values: 

outy

 = 4 for using J1 relay in on/off mode; 

Hy

 = 5; 

SV

 = 200° F. 

Note: if this is to control a contactor with 24 V coil, PID mode can be used. Then 
the setting should be the same as example 10.1 except the SV value. 
 

10.3 Drive a proportional control valve directly in cooling mode. 

In a cooling system where the controller is connected to a linear control valve to 
control the flow of the coolant. The target temperature is SV = 50° F. An PT100 
RTD sensor is used to measure the temperature. A 120 V buzzer is connected to 
the J1 relay which works as an absolute high temperature alarm, which should be 
triggered at 54° F. 
   
a. Wiring diagram 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

L

N

S

Linear control valve

0-20mA or 4-20mA

120VAC

Fuse

RTD

R

R

W

Alarm

120V buzzer

+

-

 

Figure 12a. A wiring example for controlling a proportional valve (0-20mA or 4-
20mA).   

6

7

8

9

10

11

12

13

14

1

2

3

4

5

L

N

S

Linear control valve

0-5Vdc or 1-5Vdc

120VAC

Fuse

RTD

R

R

W

Alarm

120V buzzer

+

-

250 Ohms 

Resistor

 

Figure 12b. A wiring example for controlling a proportional valve (0-5Vdc or 1-
5Vdc). One 250 Ohms resistor is required (not included).    
 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

L

N

S

Linear control valve

0-10Vdc or 2-10Vdc

120VAC

Fuse

RTD

R

R

W

Alarm

120V buzzer

+

-

500 Ohms 

Resistor

 

Summary of Contents for SYL-2381-mA

Page 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Page 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Page 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Page 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Page 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Page 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Page 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Reviews: