background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2021.05                                                                    

   

                                                       P3/7 

 

Table 1. System configuration parameters. 

Code 

Description 

Setting Range 

Initial  

Note 

Inty 

Inty 

Input Sensor Type 

See Table 2  

outy 

outy 

Control Output 

Mode 

1, 2, 3, 4, 5, 6 

Coty 

coty 

Main Output Mode 

0 - 20 mA,  
4 - 20 mA,  

SSR (does not apply 

to this model) 

0 -  20 

mA 

Hy 

Hy 

Hysteresis Band 

0 ~ 9999 

PSb 

PSb 

Input Offset 

-100 ~ 100 (deg.) 

rd 

rd 

Control Direction 

0: heating; 1: cooling 

  

CorF 

CorF 

Display Unit 

C, F      

  

Id 

Id 

Unit ID 

1 ~ 64 

baud 

bAud 

Baud Rate 

1200, 2400, 4800, 

9600 

9600 

End 

End 

Exit 

  

  

  

 
 

Note 1.

 The controller is preset for K type thermocouple input. If any other type of 

sensor is used, the 

Inty

 value needs to be changed to the corresponding symbol 

as shown in Table 2. 
 

Table 2. Temperature sensor code. 

Symbol 

Description 

Working Temperature Range 

TC, Type T 

-200 ~ 400° C; -320 ~ 752° F 

TC, Type R 

-50 ~ 1600° C; -58 ~ 2900° F 

TC, Type J 

-200 ~ 1200° C; -320 ~ 2200° F 

WRE 

WRe 

TC, WRe 3/25 

0 ~ 2300° C; 32 ~ 4200° F 

TC, Type B 

350 ~ 1800° C; 660 ~ 3300° F 

TC, Type S 

-50 ~ 1600° C; -58 ~ 2900° F 

TC, Type K 

-200 ~ 1300° C; -320 ~ 2400° F 

TC, Type E 

-200 ~ 900° C; -320 ~ 1650° F 

P100 

P100 

RTD, Pt100 

-200 ~ 600° C; -320 ~ 1100° F 

P10

.

P10.0 

RTD, Pt100 

-99.9 ~ 600.0° C; -99.9 ~ 999.9° F 

Cu50 

Cu50 

RTD, Cu50 

-50.0 ~ 150.0° C; -60 ~ 300° F 

 
 

Note 2.

 The setting of 

outy 

determines the control output mode. When it is set 

to:  
1 - J1 relay works as absolute alarm output; mA port as PID control output;  
2 - J1 relay works as derivation alarm output; mA port as PID control output; 
3 - J1 relay works as PID control output; mA port disabled; 
4 - J1 relay works as on/off control output; mA port disabled; 
5 - J1 relay works as absolute alarm output; mA port disabled. 
 

Note 3. 

The setting of 

Coty

 determines the main output modes on the mA port 

(terminal 7 & 8). When it is set to:

 

“0

-

20”

 - Main output is set to 0 - 20 mA linear current output mode. 

“4

-

20” 

- Main output is set to 4 - 20 mA linear current output mode. 

“SSR”

 - Not available on SYL-2381-mA. 

 
Note 4. 

Hysteresis Band 

Hy

 (also called dead band, or differential) is used in on/off 

control mode. Its unit is in degrees (

°

C or 

°

F). When the controller works in on/off 

control mode for heating, the output will be off when PV > SV and on again when 
PV < (SV - Hy). When the controller works in on/off control model for cooling, the 
output will be off when PV < SV and on again when PV > (SV + Hy).  
 

Note 5

. Input offset 

PSb

 is used to set an input offset to compensate the error 

produced by the sensor. For example, if the meter displays 3ºC when probe is in 
ice/water mixture, setting 

PSb

 = -3, will make the controller display 0ºC. To set a 

negative value, use Shift (>) key to go to the very left digit, then press Down key 
(V) until the first digit change to 

-

”.

 

 

Note 6. 

Parameter 

ID

 and 

bAud

 are used for RS485 communication. For details, 

please check the supplementary manual. 

 

 

5.2 PID parameters (accessed by code 0036) 

The PID control parameters are listed in Table 3. To change the parameters, press 
SET key, en

ter code “0036”, and press SET 

key again. The operation to change 

these parameters is similar to what is shown in the flow chart in Figure 3. 
 
The  values  of  the 

P

I

,  and 

D

  parameters  are  critical  for  good  response  time, 

accuracy, and stability of the system. Using the Auto-tune function to automatically 
determine these parameters is recommended for the first-time users. If the auto-
tuning result is not satisfactory, you can manually fine-tune the PID constants for 
improved performance. 
 

Table 3. PID parameters. 

Symbol 

Description 

Setting Range 

Initial  

Note 

Proportional 

Constant 

0.1 ~ 9999.9 

5.0 

Integral Time 

2 ~ 1999 (sec) 

100 

Derivative Time 

0 ~ 399 (sec) 

20 

End 

End 

Exit 

  

  

   

 
 

Note 7.

 Proportional Constant (

P

): Also called Proportional Band. Its unit is degree. 

If 

CorF

 is set to ° F, the unit of P is 1° F. If 

CorF

 is set to ° C, the unit of P is 1° C. 

Assuming the set temperature 

SV 

is set to 200° F, Proportional Constant 

P

 is set 

to 5.0. When integral (

I

) and derivative (

d

) actions are both removed, i.e., 

I

 = 0 and 

d

 = 0, the controller

’s

 output should change from 100% to 0% as the temperature 

increases from 195° F to 200° F. The smaller the 

P

 value, the stronger the action 

will be for the same amount of temperature difference between 

SV

 and 

PV

 

Note 8.

 Integral Time (

I

): Brings the system up to the set value (

SV

) by adding to 

the output that is proportional to how far the process value (

PV

) is from the set 

value (

SV

) and how long it has been there. When 

I

 is set to a smaller value, the 

response speed is faster but the system is less stable. When 

I

 is set to a larger 

value, the respond speed is slower, but the system is more stable. 
 

Note 9

. Derivative Time (

d

): Responds to the rate of process temperature (PV) 

change, so that the controller can compensate in advance before the difference 
between 

SV

 and 

PV

 (|

SV

 - 

PV

|) gets too big. A larger 

d

 value increases its action. 

Setting 

d

 value too small or too large would decrease the stability of the system, 

cause oscillation, or even make the system non-convergent. 
 
 

5.3 Control parameters 

The control parameters are listed in Table 4. To change the parameters, press 
they 

SET key, enter code “0038”, 

then press the SET key again. The procedures 

to change control parameters are similar to what is shown in Figure 3. 
 
 
 

Summary of Contents for SYL-2381-mA

Page 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Page 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Page 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Page 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Page 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Page 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Page 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Reviews: