42
A-A
B-B
A
A
B
B
E
E
VISIO 2 (uden afd
æ
kning)
Panel indbygning
Uden tekst
20
0
42
English
RAIS/
attika
- User manual for VISIO
Installation height
min. 385 mm
ATTENTION!
Insulated chimney (acc.) all
the way down to the collar
Distance from reflector to
back wall (see table)
Distance from front glass to
furniture min. 1200 mm
Reflector plate
Clearance height above
burning chamber
min. 698 mm
Panel type
Distance to back wall
12.5 mm Fermacell with
25 mm brandbats
75 mm
50 mm
calcium silicate boards
62.5 mm
Convection area is placed
just below the sloped plate.
To guide the hot air out of
the convection outlets, RAIS
recommends to mount a
sloped, non-combustible and
insulating plate (Fer
mineral wool or similar) above
the outlets.
Fermacell is facing down.
VISIO 2 - installation distances - panels