28
The variant of connection with the accumulation tank
ATTACK
DP
boiler
Regumat
ATTACK-
-OVENTROP
Heating
system
THE
ACCUMULA
TION
T
ANK
STORAGE TANK
FOR DHW
The pump
Expansion vessel
the return flap
The boiler has to be operated continuously in nominal output. In case of heat outlet when the boiler operates
on a lower output that the nominal, it is necessary to attach the boiler to the accumulation tank
of the volume of min. 460 litres (STN EN 303-5, paragraph 4.2.5 ).
1. Regumat is used to increase the reurn heating water temperature returning into the boiler to
more than 65°C. The return water temperature below 60°C causes increasing formation of
condensate and the tar, and then decreasing of boiler durability.
Technical parameters:
Clarity
DN25
Max.pressure 10 bar
Max.temperature 120°C
Value kvs 3,9
Clarity
DN32
Max.pressure 10 bar
Max.temperature 110°C
Value kvs 0
Regumat consists of three-way mixing valve, circulation pump, closting cock, thermometers
and insulation. The advantage of this solution consists in its compactness, simplicity of
attendance and in guarranteed protection of the boiler thermal exchanger.
Regumat for the boiler Ordering code
ATTACK DP25, DP35 (DN25) DPP25003
ATTACK DP45, DP75, DP95 (DN32) DPP25006
The variants of protection and boiler durability increase
1
2
4
3
1
2
4
3