2 / 26
1.3
Specifications
Measuring Range
Height: Up to 99.999m, 0.001 resolution, ± 0.1% accuracy
Volume: Up to 99999m
3
, 0.001 resolution, ± 0.1% accuracy
Tank Selection
Wide range of tank selection available (cube, cuboid,
cylinder, horizontal cylinder and other customized options)
with user programmable dimensions
Display Units
Unit selection as per requirement. Height: meters. Volume:
cubic meters, liters, gallons. Loop current: mA
Sensor and Medium
User selectable medium Specific Gravity with corresponding
sensor setting in meters
Micro SD Card for Data
Acquisition
Micro SD card installed for data acquisition functionality at
user defined time intervals
RS 485 Communication
RS 485 based communication with desktop application. AT
Systems Level Software for microSD data retrieval, live data
monitoring and data analytics
Analog Input Calibration
Factory calibrated 4-20mA analog input for sensor
connection, with in-field calibration functionality
Clock
Internal clock and calendar, 24 Hour format,
±
1 min/month
accuracy
Volume Totalizer
Logging of total volume consumed, up to 999,999,999 liters
Security Settings
Password enable feature for write protection of critical
parameters
Relays
2x relays with independent manual and auto operation.
Rating: 277VAC, 125VDC-Max, 5A
Relay Auto Modes
Auto Mode 1: Level based turn-on and turn-off set points
with inverse logic functionality
Auto Mode 2: Time based turn-on and turn-off modes
Device ID
Unique device ID allocation for interfacing multiple
controllers with
AT Systems
Level Software
Panel Cutout Size
L x W (93mm x 93mm)
Dimensions (Volume Based)
L x W x D (113.5mm x 113.5mm x 83mm)
IP Class Protection
IP 65 (In Panel Mount Installation)
Weight (Assembly)
≈ 255 Grams
Power Requirement
24 VDC with high voltage, polarity and short circuit
protection
Note:
Dual sensor option and customized solution also available at user request.