5.4.2
Room thermostat on/off
1.
Connect the room thermostat. See § 5.4.1.
2.
The terminal block for the connection for a volt free room thermostat, or
time clock, is X4 on the control panel. The terminals are wired to the
input circuit of the control unit, which has its own 24V dc ‘wetting
voltage’
.
3.
If using a room thermostat with heat accelerator, this must be set at
0·1A.
4.
The maximum permissible resistance of the room thermostat circuit
and cable is 15 Ohms.
5.
Where a 'wireless' room thermostat is employed, consult the
manufacturer’s instructions for installation.
Note - Under no circumstances must any electrical power be input to
the room thermostat terminals. It is a volt-free switch.
Note - Care must also be taken to avoid induced voltages caused by
the running of the thermostat cables along side mains voltage cables.
5.4.3
Outside temperature sensor
The appliance has a connection for an outside temperature sensor. The
outside temperature sensor can be applied in combination with an on/off
room thermostat.
Connect the outside temperature sensor. See § 5.4.1.
See Weather-dependent control § 7.6 for the setting of the CH
temperature line.
23