4.4
Boiler location
The appliance can be fitted to a mounting frame. The assembly or just
the appliance should be mounted to a wall with sufficient bearing
strength.
In case of light wall constructions, resonance sounds may occur. There
must be an earthed electrical supply within a distance of 1 m from the
appliance. If the appliance is installed as an open appliance, the
installation room should have been provided with the required openings
for the boiler air supply.
In order to avoid freezing of the condensate discharge, the appliance
should be installed in a frost-free room.
Keep 5 cm free space above the appliance in order to be able to remove
the front panel from the casing.
4.4.1
Installation in a kitchen cupboard
Make sure there is sufficient ventilation above and below the appliance.
When the appliance is placed in a small cupboard, ventilation openings
of at least 50 cm
2
must be made.
4.4.2
Installation in an airing cupboard
Compartment ventilation is not required for a standard airing cupboard
(eg 0.6 x 0.6 x 2.3m high).
4.4.3
Remove front panel
Remove the pipework cover and the front panel for carrying out work on
the appliance as follows:-
1.
Remove the pipework cover (A), if used, forwards.
2.
Unscrew both screws (B) at the bottom of the appliance.
3.
Lift the front panel (C) and remove it forwards.
16