The following keys are provided for user monitoring and editing:
– ESC - Escape key
This key is used to select Monitor, Program, Review, or Setup
modes. It may be pressed to return to the previous function at any
time.
– SCROLL - Scroll key
From the automatic monitoring mode, pressing the left or right
SCROLL key allows the desired phase-to-phase, phase-to-neutral,
or average set of values to be displayed on the LCD. Press ESC to
return to automatic monitoring.
In the Review, Program, or Setup modes, the Scroll key allows for-
ward or reverse display of the various menu selections.
– SELECT - Select key
Pressing the Select key places the unit in the mode or data entry
point shown on the LCD display.
– INCREASE / DECREASE - Increase and Decrease keys
When a data entry is selected, the value is changed by depressing
the Increase or Decrease key.
– ENTER - Enter key
When a desired data entry value is displayed, pressing the ENTER
key will place the value in the program.
Also, pressing ENTER during the monitor mode will stop the dis-
play from scrolling. Pressing ENTER again causes scrolling to
resume.
During initial power up, the Liquid Crystal Display (LCD) on the
Keypad/Display Panel displays the panel revision level, then re-
verts to automatically scrolling through the measured phase-to-
phase, phase-to-neutral, and average values.
23(5$7,1*,16758&7,216
&
211(&7,1*
*
(1(5$7256
$1'
6$3(
8
1,76
The following picture gives an overview of the connections to be
made between two SAPE units and two QAS-generators.
3&3RZHUFRQWUROFXELFOH
&%&RQWDFWRUER[
'37RWKHVLWHGLVWULEXWLRQSDQHO
Prior to starting parallel operation of two generators,
following con-
nections need to be made
:
1. Connect the communication cable between the generator QAS 1
and the stand alone paralleling equipment SAPE 1 (socket X33). Do
the same for QAS 2 and SAPE 2.
2. Connect the communication cable between SAPE 1 and SAPE 2 or
QAS with integrated paralleling (socket X30 or X31).
3. Route the power cables of the QAS through the bottom hole of the
contactor box of the SAPE and connect them with the contactor
(strips L1, L2, L3, N and PE on the left-hand side).
PHASE
KWATT
Barber
Colman
KVAR
PF
-180
+180
VOLTS
AMPS
HERTZ
INC
ESC
SCROLL
SCROLL
DEC
ENTER
SELECT
COMMAND MODE
HIGH LIMIT
LOW LIMIT
BLEND MODE
LOAD GENERATOR
UNLOAD GENERATOR
BREAKER TRIP
SYNCH ENABLE
VOLT NOT MATCHED
FREQ NOT MATCHED
PHASE NOT MATCHED
FORWARD POWER ON
FORWARD POWER OFF
REVERSE POWER ON
BREAKER CLOSED
When connecting two standard generators in paral-
lel, two SAPE units must be used.
Each SAPE has two of these connections, to enable
paralleling more than two generators.
Always connect strips L1 with L1, L2 with L2 and
L3 with L3!