This switch allows for three positions:
– ILS (Isochronous Load Sharing): both connected genera-
tors give their full proportional load immediately
– Blend: the proportional load of the brought in generator is
slowly built up (time adjustable between 2 s and 5 min), af-
ter selector switch S6 has been set to ‘Load’
– Command: allows a fixed power output of the generator,
irrespective of the load
6 6HOHFWRUVZLWFK8QORDG/RDG
This switch only applies to the ‘Blend’ mode (selector switch
ILS/Blend/Command in position ‘Blend’).
The central position of the three position selector switch is used
for ‘ILS’ mode. The other two positions are:
– Unload: one generator is enough to supply the full load, but
to prevent the other generator from idling, it still supplies
± 10 % (adjustable value) while the other one supplies
± 90 % of the full load
– Load: both connected generators deliver equal percentages
of their full load capacity
6 %UHDNHU&RQWDFWRUFORVHHQDEOH
Allows the circuit breaker/contactor of the second unit to be
closed if all conditions are fulfilled.
6 %UHDNHU&RQWDFWRUFORVH
Manually closing of the circuit breaker/contactor of the first
unit, after S18 (Breaker/Contactor close enable) has been
pushed.
6 %UHDNHU&RQWDFWRURSHQ
Opens the circuit breaker/contactor of the unit.
6 (PHUJHQF\VWRSEXWWRQ
Push the button to stop the unit in case of an emergency. When
the button is pressed, it must be unlocked, by turning it anti-
clockwise, before the unit can be restarted.
7 7UDQVIRUPHUJHQVHWYROWDJH
7 7UDQVIRUPHUEXVYROWDJH
; &RQQHFWRU;
Connector for communication with the power control module
of another SAPE unit or QAS with integrated paralleling.
; &RQQHFWRU;
Connector for communication with the power control module
of another SAPE unit or QAS with integrated paralleling.
; &RQQHFWRU;
Connector for communication between the SAPE power con-
trol module and the SAPE contactor.
; &RQQHFWRU;
Connector for communication between the power control mod-
ule of the SAPE unit and the generator.
&
217$&725
%
2;
. &RQWDFWRUIRUJHQVHWSDUDOOHOLQJ
; &RQQHFWRU;
Connector for communication between the SAPE power con-
trol module and the SAPE contactor.
Several SAPE units can be connected to each other,
as the power control module of each SAPE unit has
got two connectors (X30 and X31).