Storage of the generator
7.1
Storage
– Store the generator in a dry, frost-free room which
is well ventilated.
– Run the engine regularly, e.g. once a week, until it
is warmed up. If this is impossible, extra
precautions must be taken:
• Consult the engine’s operator manual.
• Remove the battery. Store it in a dry, frost-free
room. Keep the battery clean and its terminals
lightly covered with petroleum jelly. Recharge
the battery regularly.
• Clean the generator and protect all electrical
components against moisture.
• Place silica gel bags, VCI paper (Volatile
Corrosion Inhibitor) or another drying agent
inside the generator and close the doors.
• Stick sheets of VCI paper with adhesive tape
on the bodywork to close off all openings.
• Wrap the generator, except the bottom, with a
plastic bag.
7.2
Preparing for operation after
storage
Before operating the generator again, remove the
wrapping, VCI paper and silica gel bags and check the
generator thoroughly (go through the checklist
“Before starting” on page 26).
– Consult the engine’s operator manual.
– Check that the insulation resistance of the
generator exceeds 5 M
.
– Replace the fuel filter and fill the fuel tank. Vent
the fuel system.
– Reinstall and connect the battery, if necessary
after being recharged.
– Submit the generator to a test run.
Summary of Contents for QAS 60 Pd
Page 1: ...QAS 60 Pd S2A APP Instruction Manual for AC Generators English...
Page 2: ......
Page 111: ...111 Circuit diagrams...
Page 115: ...115...
Page 119: ...119...
Page 128: ...128...
Page 132: ...132...
Page 139: ...139...
Page 141: ......
Page 142: ...Printed in Belgium 04 2012 2954 6280 00 www atlascopco com...