- 85 -
Rated voltage 3ph line to line
400 V
480 V
Rated voltage 3ph line to line lower voltage (optional)
230 V
-
Rated current 3ph
469 A
415 A
Rated current 3ph lower voltage (optional)
816 A
-
Performance class (acc.ISO 8528-5:1993)
G2
G2
Single step load acceptance (0-PRP)
55%
75%
143 kW
207 kW
Frequency droop
<5%
<5%
isochronous
isochronous
Fuel consumption at 0% load
6.07 kg/h
8.85 kg/h
Fuel consumption at 50% load
29.07 kg/h
34.10 kg/h
Fuel consumption at 75% load
41.41 kg/h
48.65 kg/h
Fuel consumption at full load (100%)
54.92 kg/h
62.29 kg/h
Specific fuel consumption at full load (100%)
0.211 kg/kWh
0.266 kg/kWh
Fuel autonomy at full load with standard tank
9 h
8 h
Fuel autonomy at full load with optional 24 hrs tank
25 h
22 h
Max. oil consumption at full load
0.04 l/h
0.04 l/h
Maximum sound power level (LWA) measured according to
2000/14/EC OND (measured at 75% PRP load)
97 dB(A)
-
Useful capacity of fuel tank
603 l
603 l
Useful capacity of optional 24 hrs fuel tank
1709 l
1709 l
Single step load capability (O-PRP) Qc1002-Qc2002
100%
100%
208 kW
276 kW
Single step load capability (O-PRP) Qc4002
80%
100%
260 kW
276 kW
Application data
Mode of operation
PRP
PRP
Site
land use
land use
Operation
single/parallel
single/parallel
Start-up and control mode
manual/automatic
manual/automatic
Start-up time
unspecified
unspecified
Mobility/Config. acc. to ISO 8528-1:1993
transportable/D
transportable/D
Mounting
fully resilient
fully resilient
Climatic exposure
open air
open air
Summary of Contents for QAS 275-325
Page 1: ...QAS 275 325 Volvo S2A APP Instruction Manual for AC Generators English...
Page 2: ......
Page 91: ...91 Circuit diagrams...
Page 95: ...95...
Page 99: ...99...
Page 103: ...103...
Page 107: ...107...
Page 112: ...112...
Page 113: ......
Page 114: ...Printed in Belgium 11 2010 2954 3880 01 www atlascopco com...