- 60 -
Connecting the generator
Precautions for non-linear and
sensitive loads
The most common non-linear, 3-phase loads are
thyristor/rectifier-controlled loads, such as convertors
supplying voltage to variable speed motors,
uninterruptable power supplies and Telecom
supplies. Gas-discharge lighting arranged in single-
phase circuits generate high 3rd harmonics and risk
for excessive neutral current.
Loads most sensitive to voltage distortion include
incandescent lamps, discharge lamps, computers, X-
ray equipment, audio amplifiers and elevators.
Consult Atlas Copco for measures against the adverse
influence of non-linear loads.
Quality, minimum section and
maximum length of cables
The cable connected to the terminal board of the
generator must be selected in accordance with local
legislation. The type of cable, its rated voltage and
current carrying capacity are determined by
installation conditions, stress and ambient
temperature. For flexible wiring, rubber-sheathed,
flexible core conductors of the type H07 RN-F
(Cenelec HD.22) or better must be used.
The following table indicates the maximum allowable
3-phase currents (in A), in an ambient temperature of
40°C, for cable types (multiple and single core PVC
insulated conductors and H07 RN-F multiple core
conductors) and wire sections as listed, in accordance
with VDE 0298 installation method C3. Local
regulations remain applicable if they are stricter than
those proposed below.
The lowest acceptable wire section and the
corresponding maximum cable or conductor length
for multiple core cable or H07 RN-F, at rated current,
for a voltage drop e lower than 5% and at a power
factor of 0.80, are respectively 2.5 mm² and 144 m. In
case electric motors must be started, oversizing the
cable is advisable.
The voltage drop across a cable can be determined as
follows:
e = Voltage drop (V)
I = Rated current (A)
L = Length of conductors (m)
R = Resistance (
/km to VDE 0102)
X = Reactance (
/km to VDE 0102)
Connecting the load
Site distribution panel
If outlet sockets are provided, they must be mounted
on a site distribution panel supplied from the terminal
board of the generator and in compliance with local
regulations for power installations on building sites.
Non-linear loads draw currents with
high contents in harmonics, causing
distortion in the wave form of the
voltage generated by the alternator.
Wire section
Max. current (A)
(mm
²
)
Multiple core
Single core
H07 RN-F
25
94
101
88
35
114
123
110
50
138
155
138
70
176
191
170
95
212
228
205
120
245
273
239
150
282
314
275
185
323
358
313
240
379
421
371
300
429
477
428
e
3 I L
R
cos
X
sin
+
1000
------------------------------------------------------------------------------
=
Summary of Contents for QAS 275-325
Page 1: ...QAS 275 325 Volvo S2A APP Instruction Manual for AC Generators English...
Page 2: ......
Page 91: ...91 Circuit diagrams...
Page 95: ...95...
Page 99: ...99...
Page 103: ...103...
Page 107: ...107...
Page 112: ...112...
Page 113: ......
Page 114: ...Printed in Belgium 11 2010 2954 3880 01 www atlascopco com...