3.22 Calling up/modifying the unit of temperature
Control panel
Starting from the Main screen:
• Press Scroll button (12) until <P.07> is shown and then press Enter button (13). The actually used
unit is shown. Possible settings are <˚C> and <˚F>.
• Press Enter button (13) (unit blinks) and use the Scroll buttons (12) to select another unit of
temperature.
• Press Enter button (13) to program the new unit or press Escape button (14) to return to the parameter
screen without changes.
3.23 Calling up/modifying unit of pressure
Control panel
Starting from the Main screen:
• Press Scroll button (12) until <P.08> and the possible settings are shown (<Mpa>, <psi>, and <bar>).
Press Enter button (13) and the actually used unit is shown.
• Press Enter button (13) (unit starts blinking) and use the Scroll buttons (12) to select another unit of
pressure.
• Press Enter button (13) to program the new unit of pressure. Press the escape button (14) to return to
the parameter screens.
3.24 Activating automatic restart after voltage failure
Description
This function allows the compressor to restart automatically after a power failure.
This parameter, accessible in screen <P. 9>, can only be modified after entering a code. Consult your
supplier if this function is to be activated.
For compressors leaving the factory, this function is made inactive. If desired, the function can be
activated. The ARAVF label 1079 9932 74( see section Pictographs ) shall be glued near to the controller.
Consult your local supplier.
Instruction book
2920 7180 30
51
Summary of Contents for GA 30+
Page 1: ...Atlas Copco Oil injected rotary screw compressors GA 30 GA 37 GA 45 Instruction book ...
Page 2: ......
Page 15: ...Motor side view GA 30 up to GA 45 Pack Instruction book 2920 7180 30 13 ...
Page 16: ...Service side view GA 30 up to GA 45 Pack Instruction book 14 2920 7180 30 ...
Page 17: ...Motor side view GA 30 up to GA 45 Full Feature Instruction book 2920 7180 30 15 ...
Page 188: ......
Page 189: ......