Temperature input
Minimum
setting
Nominal
setting
Maximum
setting
Water inlet temperature of energy recovery
˚C
0
50
99
Water inlet temperature of energy recovery
˚F
32
122
210
Energy recovery water outlet temperature
˚C
0
Depends on
application
99
Energy recovery water outlet temperature
˚F
32
Depends on
application
210
To modify a setting, consult the relevant section in the description of the controller.
Recoverable energy
The recoverable energy can be calculated from:
RECOVERED ENERGY (kW) = 4.2 x water flow (l/s) x water temperature rise (˚C)
In the tables below, typical examples are given.
Data for low temperature rise/low water flow systems
Parameter
Unit
GA 30
+
GA 37
GA 45
Recoverable energy
kW
27.5
32.5
39.5
Recoverable energy
hp
36.8
43.5
53
Water flow
l/min
39.4
46.6
56.6
Water flow
cfm
1.4
1.6
2
Temperature at inlet
˚C
50
50
50
Temperature at inlet
˚F
122
122
122
Temperature at outlet
˚C
60
60
60
Temperature at outlet
˚F
140
140
140
Data for high temperature rise/low water flow systems
Parameter
Unit
GA 30
+
GA37
GA 45
Recoverable energy
kW
27.5
32.5
39.5
Recoverable energy
hp
36.8
43.5
53
Water flow
l/min
5.5
6.5
7.9
Water flow
cfm
0.19
0.23
0.28
Temperature at inlet
˚C
20
20
20
Temperature at inlet
˚F
68
68
68
Temperature at outlet
˚C
92
92
92
Temperature at outlet
˚F
197
197
197
Instruction book
2920 7180 30
125
Summary of Contents for GA 30+
Page 1: ...Atlas Copco Oil injected rotary screw compressors GA 30 GA 37 GA 45 Instruction book ...
Page 2: ......
Page 15: ...Motor side view GA 30 up to GA 45 Pack Instruction book 2920 7180 30 13 ...
Page 16: ...Service side view GA 30 up to GA 45 Pack Instruction book 14 2920 7180 30 ...
Page 17: ...Motor side view GA 30 up to GA 45 Full Feature Instruction book 2920 7180 30 15 ...
Page 188: ......
Page 189: ......