53
06: Bypass voltage range setting
Interface
Setting
Press the Down key or Up key to set the
acceptable high point and acceptable low
point of input voltage:
HLS:
High loss voltage in Line
mode (the setting range is from
230Vac to 264Vac of the nominal
voltage).
LLS:
Low loss voltage in Line mode
(the setting range is from 170Vac to
220Vac of the nominal voltage).
00: Exit setting
02: Frequancy Converter Enable/Disable (Only for A03-OP3451)
Interface
Setting
CF ENA:
FC mode enable.
CF DIS:
FC mode disable.
03: Output Frequency Setting (Only for A03-OP3451)
Interface
Setting
You may set the initial frequency on battery
mode:
BAT 50:
presents output frequency is
50Hz
BAT 60:
presents output frequency is
60Hz
If converter mode is enabled, you may
choose the following output frequency:
CF 50:
presents output frequency is
50Hz
CF 60:
presents output frequency is