Electrical connection
7.
It is recommended to read the warnings at the beginning of the document.
7.1. Recommendations/Safety instructions
Refer to the wiring diagram on the back of the cover.
The water heater can only be turned on when it is filled with water, see "Filling the water heater" -
"Installation". We recommend installing a continuous power supply to the water heater in order to
optimize the performance of the product.
The electrical connection must be made with the power turned off by a qualified professional.
The water heater must be connected to a 230 V single phase 50 Hz AC mains.
The electrical connection must comply with the NFC 15-100 installation standards and with the applicable
recommendations in the country where the water heater is installed. The installation must include:
P
A 16 A all-pole circuit breaker (minimum curve C) with contact opening of at least 3 mm.
P
Protection by a 30 mA earth-leakage circuit breaker.
In no case should the safety thermostat on the electric booster pump be repaired outside our factories. Failure to
comply with this clause will void the warranty.
7.2. Operation with contact Peak hours/Off-peak hours
In this setup, the electric booster pump and the heat pump cannot function during peak hours.
See the wiring diagram on the first page.