MODBUS COMMUNICATIONS
HeatNet Control REV 3.47-1
Page 132
Figure 61
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
mode.
3) A calculated setpoint if running in
Outdoor Air Reset Mode
4) The 4-20mA (0-10V) setpoint.
30241
AvailableBoilers
16 bit signed
---
The maximum number of boilers available
to fire.
0 - 16
30242
BTUHigh16
32 bit unsigned
30243
BTULow16
30247
SystemReturnTemp
16 bit signed
---
The system return temperature (if
available). See BoilerStatus4 to determine
if the sensor is present.
32
– 250
°
F
30265
SystemFlowHigh16
32 bit unsigned
0.01
Boiler SystemFlow High (Upper) and Low
(Lower) 16-bit registers. To get Boiler
SystemFlow High (Upper) and Low (Lower)
16-bit registers. To get the actual
SystemFlow, the high and low 16-bit
registers must be combined (concatenated)
into a single 32-bit counter as:
SystemFlowHigh16: SystemFlowLow16
Example
SystemFlow = ((SystemFlowHigh16 *
65536) + SystemFlowLow16) * 0.01
This value is either the system flow meter
reading or the value written to the
BMSFlowRateGPM register by the BMS.
0-1500 GPM
30266
SystemFlowLow16
30269
HeatingBoilersOn
8 bit unsigned
---
The number of boilers currently running for
heating.
0
– 16
30270
DHWBoilersOn
8 bit unsigned
---
The number of boilers currently running for
DHW.
0
– 16
30271
ManualBoilersOn
8 bit unsigned
---
The number of boilers currently running
due to a local override, T1, T2, AA/High
Fire, etc.
0
– 16
30369
Boiler 1 Local Flow
16 Bit Signed
.1
Boiler (1
–16)
0-3,276
30370
Boiler 2 Local Flow
16 Bit Signed
.1
Boiler 01 = Master
0-3,276
30371
Boiler 3 Local Flow
16 Bit Signed
.1
or “Connected Boiler”
0-3,276
30372
Boiler 4 Local Flow
16 Bit Signed
.1
Local Flow Rate for Each Boiler
0-3,276
30373
Boiler 5 Local Flow
16 Bit Signed
.1
0-3,276
30374
Boiler 6 Local Flow
16 Bit Signed
.1
0-3,276
30375
Boiler 7 Local Flow
16 Bit Signed
.1
0-3,276
30376
Boiler 8 Local Flow
16 Bit Signed
.1
0-3,276
30377
Boiler 9 Local Flow
16 Bit Signed
.1
0-3,276
30378
Boiler 10 Local Flow
16 Bit Signed
.1
0-3,276
30379
Boiler 11 Local Flow
16 Bit Signed
.1
0-3,276
30380
Boiler 12 Local Flow
16 Bit Signed
.1
0-3,276
30381
Boiler 13 Local Flow
16 Bit Signed
.1
0-3,276
30382
Boiler 14 Local Flow
16 Bit Signed
.1
0-3,276
30383
Boiler 15 Local Flow
16 Bit Signed
.1
0-3,276
30384
Boiler 16 Local Flow
16 Bit Signed
.1
0-3,276