DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3 3.x
Page 108
POST PURGE TIME
2 minutes
(1-60min)
Time in minutes to keep local circ. pump on after boiler stops
ALWAYS ENABLED
OFF
Pump never shuts off.
LOCAL PUMP VFD
OFF
ON, OFF
ON = Outputs a 0-10VDC or 4-20mA signal from J4 pins 1 & 5 that
is proportional to the fire rate of the boiler. Connect to a VFD
controlling a Local pump.
FLOW PROVE
10s
10-240 sec
This is an adjustable flow proving time to allow slower valves to
open before proving flow.
MASTER
PUMP/VALVE
REMAINS ON
OFF
ON/OFF
ON = The MASTER boiler will keep its pump/valve on when no
boilers are running. Prevents deadheading the system flow.
SETBACK TABS 1 - 4
1
(1
– 4)
Four setbacks (TABBED) to adjust setpoint during a time period
ENABLE
OFF
ON, OFF
Enable or disable the use of this setback
SETBACK
20
°
F
(0
– 50
°
F)
Temporarily subtracts this temp from the setpoint
START DAY
MON
Day of the week to begin setback or a day range
START TIME
12:00AM
Time to begin setback
END DAY
MON
Day of the week to end the setback or a day range
END TIME
12:00AM
Time of the day to end the setback
Display Units
English
English, Metric
English =
°
F, Metric =
°
C
(Follows Above Setting)
GPM
GPM, LPM
Gallons Per Minute/Liters Per Minute