DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3 3.x
Page 114
Control Settings Menu
— Page 2
CONTROL
H-Net
Displays method of operation: HeatNet (H-Net)
H-NET MASTER
YES
Auto detected, based on the HEADER sensor.
If the HEADER sensor is present and is set to TYPEZ, the KN-
Series control is run as an H-Net MASTER (YES).
If the HEADER sensor is not TYPEZ, H-Net MASTER = NO.
MASTER TYPE
AUTO
AUTO,
COMBINATION,
DHW
Two PID controls are provided, one for Space heating and one for
DHW heating. This menu item selects how they are to be used. The
MASTER TYPE setting is used to determine if the MASTER
control is to be used as a space heating control, a combination
DHW/space heating control, or just to perform DHW Heating.
When set to AUTO, the boiler uses one PID control to provide space
heating. When set to COMBINATION, the control will use two
independent PID controls to provide space heating and DHW
heating. When set to DHW, the control only uses the DHW PID
control.
HEATNET ADDRESS
255
(2
–16)
The local address is the address of a MEMBER device. This is
normally in the range of 2 through 16. But if the KN-Series control
is a MASTER, then the default address is 255. The H-NET
ADDRESS # is synonymous with boiler #.
SPACE HEATING
DHW HEATING
TABS
If the MASTER TYPE is set to COMBINATION, or the DHW
BOILER? setting is set to LOCAL or COMBINATION, the
MODULAR BOILER SET is duplicated for each PID. Select