Page 6
KN INSTALLATION AND OPERATION INSTRUCTIONS
Boiler ratings and specifications
2
Boiler model
Units
K N-2
K N-4
Notes
AFUE (DOE seasonal efficiency)
%
90
N/A
1
CSA Input (Max)
Btuh
Kw
199,999
59
399,999
116.8
2
CSA Input (Min)
Btuh
Kw
40,000
11.7
80,000
23.4
2
Maximum allowable working pressure
PSIG
kPa
100
689
Water supply and return connections
Inches, NPT
1¼
Boiler water volume
Gallons
Liters
3.9
14.8
5.9
22.3
Shipping weight
Pounds
Kg
540
245
780
354
Operating weight
Pounds
Kg
563
256
753
341
Fuels
Natural gas or propane
3
Gas connection size
Inches, NPT
½
¾
Gas supply pressure, minimum
Inches WC
mm WC
2
50.8
Gas supply pressure, maximum
Inches WC
mm WC
14
356
Vent connection size
Inches
mm
3
76.2
4
101.6
Vent options
Direct Vent or Category IV and II
Combustion air options
Air from boiler room or
ducted to boiler from outside
Combustion air adapter size
Inches
mm
3
76.2
4
101.6
Electrical requirements
Voltage
120 vac/60 hz/1-phase
Current draw (120-volt power line)
Amperes
2.5
5
Thermostat anticipator setting
Amperes
0
5
Operating control
HeatNet control
4
Control operation options
Stand-alone
HeatNet
BMS (boiler management system)
4
Control methods
Heat demand (HeatNet or stand-alone)
On/Off
BMS (4-20 ma input)
Staging
RS485 digital communication
4
Notes
1
2
3
4
5
DOE Heating capacity is based on standard tests specified by the United States Department of Energy.
All capacity ratings above are based on sea level. Input adjustments allow setting the high fire input and may compensate for moderate altitudes.
For higher altitudes the maximum boiler input will be derated slightly.
The gas valve is capable of operating with natural gas or LP. See instructions in this manual to adjust for the specific fuel used.
For additional information, refer to the
K N
Control manual.
Thermostat anticipator setting is for a single thermostat connected to a single
K N
boiler. Also jumper from the Heat Demand terminals to the
IAR1 terminals on the connection board. See the
K N
Control manual for details.
K N-2
only