Page 43
KN INSTALLATION AND OPERATION INSTRUCTIONS
Cleaning the air filter
1. Turn the boiler on/off switch
OFF
.
2. Remove the three thumb screws that secure the filter access
plate (see Figure 33).
3. Remove the filter access plate and gasket.
4. Pull the filter clamp back and remove the air filter.
5. Inspect the filter and the filter enclosure area for dust or
debris.
6. Clean the filter, if necessary, by washing under running wa-
ter. Shake off excess water and towel dry.
If the filter enclosure and blower inlet show
signs of drywall dust, construction debris or
other deposits, you may need to inspect the
burner. Follow the procedure in this section.
Accumulation of debris in the burner can result in
burner damage and potential for severe personal
injury, death or substantial property damage.
7. If the filter is damaged or cannot be cleaned effectively,
obtain a replacement filter from your boiler distributor.
8. To replace the air filter, pull the filter clamp back, insert the
filter, and allow the clamp to secure the filter in place.
9. Replace the filter access cover gasket and access cover.
10. Replace the three thumbscrews and finger tighten securely.
11. Turn the boiler on/off switch
ON
.
Accessing the electrode assembly
1. Turn the boiler on/off switch
OFF
.
2. If the boiler ignition electrodes or flame rod appear to be
operating incorrectly, remove and inspect the assembly as
follows.
Do not remove the electrode assembly while the
boiler is operating. Allow the boiler and electrode
assembly to cool before attempting removal to
avoid possible burns. Failure to comply could
result in severe personal injury.
3. With the boiler and manual gas valve closed, remove the
upper electrical box cover (right side of boiler).
• Remove the two 1/4 inch bolts that secure the electrode/
flame rode assembly to the boiler (Figure 34).
• The electrode spacing must be 1/8 inch
(3.2 mm)
as shown
in Figure 26.
4. If the electrodes or flame rod are damaged or the tip spacing
is incorrect, replace the assembly. The electrodes are
NOT
adjustable.
5. Re-install the assembly in the boiler.
Make sure the electrode plate gasket is in good
condition and that the assembly is securely
bolted to the boiler. The combustion chamber
operates with a positive pressure. Failure to
comply could result in severe personal injury,
death or substantial property damage.
Maintenance
(continued)
13
Figure 33
Accessing the air filter
Figure 34
Electrode/flame rod assembly inspection