Control setup
8
Before control setup
Before beginning the HeatNet control setup,
remove the wires
connected to the HEAT DEMAND and DHW DEMAND terminals
on the electrical connection board (see Figure 21). These must be
removed to prevent a call for heat during the setup process.
Close the manual gas valve before proceeding to prevent any possibility
of the boiler firing during setup.
The HeatNet control display
Starting the display
1. Check all wiring to make sure it is complete and all wires are securely connected.
2. Verify that the HEAT DEMAND and DHW DEMAND wires are removed.
3. Turn on power to the boiler and then turn the boiler on/off switch ON.
4. The control will beep at least twice and the display will show the first STANDBY
display in Figure 22. Note that pushing the DOWN button on the keypad will
change the right side of the display as shown, providing information on various
setpoints and parameters.
5. The display, LOC SET, means the setpoint temperature. Figure 22 shows the
factory default values.
Accessing setup menus
1. With the display in STANDBY, press and hold the BACK key for 5 seconds.
2. The display will change to:
3. Press the SELECT key to select setup. (Note that pressing the DOWN key would
change the selection to VIEW LOG.)
4. The display will now show the first options in the setup menus:
5. Press the DOWN key to access additional menu options. Pressing the DOWN
button once will change the display to:
6. The cursor moves to the second line, indicating this option could now be selected
with the SELECT key.
7. Continuing to press the DOWN key will access these menu options:
•
BOILERS
•
SETPOINTS
•
INDOOR AIR
•
PUMP OPTIONS
•
NIGHT SETBACK
•
OPTIONS
•
LOG/RUNTIME
•
AUX FUNCTIONS
•
SYSTEM CLOCK
•
ADVANCED SETUP