Quick Start Guide
BOUTIQUE
TM
Compact and Self-AmplifiedPublic Address and Voice Alarm System
© 2019, ATEÏS, member of PAX ProAV Group
Revision History
v1.08
Page 1: ...Quick Start Guide BOUTIQUE TM Compact and Self Amplified Public Address and Voice Alarm System 2019 ATEÏS member of PAX ProAV Group Revision History v1 08 ...
Page 2: ...types of power supply input AC mains and 48VDC for battery backup via phoenix euro block connector and secondary unit by 24VDC Connection mains power Connection battery backup To activate the power supply of BTQ VMW wallmount controller connect the AC mains power first then 48VDC battery backup input If the order is not correct the BTQ VMW can not be operated Ethernet RJ45 Connect the BTQ VM4 8 co...
Page 3: ...ured by a DIP switch BTQ SL8 BTQ SG8 DPM MAIN The DIP switch of device ID is followed by the binary code with 5 digit BTQ SL8 6 digit BTQ SG8 4 digit DPM MAIN The Device ID cannot be repeated The range of ID can be set as the table on the right DIP switch BTQ SL8 1 31 BTQ SG8 0 63 DPM MAIN 0 15 Please set the ID of BTQ SL8 BTQ SG8 and DPM MAIN orderly starting by the first number How to 1 Set the ...
Page 4: ...wer amplifier The BTQ VM4 8 controllers have an internal 250W or 500W amplifier built in For system power sharing and or backup connect a second power amplifier DPA or BPA externally The BTQ SL8 secondary unit can share power amplifier from BTQ VM4 8 controller secondary units or connect to an external power amplifier Both of the controller and secondary unit are capable to handle the power up to ...
Page 5: ...er power sharing For DC battery backup power sharing connect the battery charger to BTQ VM4 8 controller and external power amplifier as the picture below The example below is using the BCU 4830A BCU 4875A battery charger and BPA or DPA power amplifier from ATEÏS Digital paging console ...
Page 6: ...ch one DPM EVA and up to 15 DPM KPD can link to one DPM MAIN by flat cable as shown above If the control signal of DPM units is not strong enough the DPM needs to connect to DLR01 digital loop repeater for expanding the distance to 250M longer And if the power of DPM units is not enough connect a 24VDC local power on DLR01 Digital Loop Repeater see the picture below Daisy chain Redundant loop 1 Co...
Page 7: ...main and secondary units ID Set the number of main controller and secondary unit and its ID in the system The ID is composed of the number of X Y X indicates the global net ID and Y is the local net ID Network Local Network for BTQ SL8 connection Max digi link units 31 Max cable length 10m between units shielded RJ45 connector STP CAT5 6 Global Network for BTQ VMxx BTQ SG8 connection Max global ne...
Page 8: ...ettings Set the number of secondary local units SL 1 Select VM8 SL block via button and press Edit to change the number of SL units 2 Press Save to apply settings 3 Press Step3 Step 3 number of remotes Set the number of DPM8 DPM T5 CD 8DF CD 16DF CD T5DF on VM8 1 1 Port 1 1 Press Edit to change the number of DPM8 DPM T5 CD 8DF CD 16DF CD T5DF 2 Press Save to apply settings Select VM8 1 1 Port 2 bl...
Page 9: ...le to have second amplifier externally for system power sharing and or backup Set the group based on the number of local net the BOUTIQUE system has The Group 1 indicates the amplifiers in the first local network the internal amplifier is belonged to CH1 the Group 2 indicates the second local network and so on 1 Press Edit to change the number of amplifier for Int amp channel and Ext amp channel i...
Page 10: ...or Calculate dummy load capacitance and DIP switch setting DLC Installation 1 Each speaker zone has A B sub zones Each sub zone requires a dummy load capacitor in the end of speaker line 2 Set the indicated number to ON position on the DIP switch 3 Press Next Step 6 monitoring Set the monitor tolerance of speaker line impedance and power amplifier 1 Press Next to apply the preset tolerance impedan...
Page 11: ... system with the broken device only 1 If the USB flash drive is connected on BTQ VM4 VM8 SG8 click Yes to use the config file from USB to replace figure 1 If the USB flash drive is not connected the system will display the alert window figure 2 2 If not using the file from USB flash drive click Skip to skip the step figure 1 figure 2 Step 1 net ID Select the netcard ID of the new BTQ VM4 VM8 contr...
Page 12: ... settings Ethernet settings Go to Menu Setting Ethernet to setup IP address Gateway Submask DNS DHCP MAC Default Setting BTQ VM4 VM8 BTQ SG8 IP address 192 168 102 125 192 168 102 124 Subnet Mask 255 255 252 0 255 255 252 0 Gateway 192 168 100 254 192 168 100 254 DNS 0 0 0 0 0 0 0 0 Please read the BOUTIQUE user manual to know the advanced configuration such as audio routing event and bell schedul...
Page 13: ...Worthing West Sussex BN14 8NW United Kingdom Tel 44 0 1903 215315 Fax 44 0 1903 215415 sales pentonuk co uk Russian Federation 115280 Moscow Leninskaya Sloboda str 26 bld 28 Business Center Slobodskoy office 122 Tel 7 495 803 3655 Fax 7 495 803 3655 info xavtel ru com ATEÏS Far East CORP Far East Asia ATEÏS Suisse SA Switzerland South East Europe No 60 Xinghua 2nd Rd Tanzi Taichung 427 Taiwan Tel ...