Installation instructions AQUAmax
®
BASIC/CLASSIC 1-75
ATB WATER GmbH, Südstraße 2, D-32457 Porta Westfalica, www.atbwater.com /
Art.-No.: 9060 0209 / Status: 17.01.2019 / Page 20 from 24
Assembly
Using the mounting materials provided secure the ATB
control
©
3 to the casing provided for this and
to a suitable, as far as possible, weather-protected position.
The ATB
control
©
3 is supplied as plug-in variant. Cabling on site is dispensed with.
For the AQUAmax® ZB with compressed aeration, the control unit is already mounted on a
mounting plate. This can be mounted directly on the wall or in an outdoor cabinet.
Next to the control unit there is a distribution box on the mounting plate to which the AQUAmax® is
connected, as well as the sockets for the control unit (and mains cable) and the compressor(s).
AQUA
max
®
ZB mounting plate for one compressor
(1-32 PE)
AQUA
max
®
ZB mounting plate for two compressors
(>32 PE)
All tasks, which nevertheless require an opening of the control unit, are to be carried out by
a qualified electrician!
ATTENTION! Before opening the ATBcontrol
©
3 and/or the connection box it/they
must be disconnected from the mains supply. Work on opened units may be
carried out exclusively by qualified electricians! Pay attention to phase-correct
connection (even with plug-in design)!
As you are concerned with an electrical plant with submerged motor units, a
separate B16 fuse and a (separate) upstream 30 mA ELCB (earth leakage circuit
breaker) is absolutely essential!
Attention is to be paid to correct laying of the protective earth conductor up to the
earthing of the building.
Compressor 1/2
Mains
AQUA
max
®
Mains
AQUA
max
®
Compressor