Installation instructions AQUAmax
®
BASIC/CLASSIC 1-75
ATB WATER GmbH, Südstraße 2, D-32457 Porta Westfalica, www.atbwater.com /
Art.-No.: 9060 0209 / Status: 17.01.2019 / Page 13 from 24
Preparation of the AQUAmax
®
AQUAmax
®
BASIC
Before locating the
AQUA
max
®
BASIC in the cesspit, check the mounting bracket for the correct,
and for the number of connected inhabitants, matching position. The lower position of the mounting
bracket is provided for 4-8, the upper for 9-16 PT (see also the stamp on the plastic bodywork). If
required, loosen the securing screw and relocate the mounting bracket.
AQUAmax
®
CLASSIC Z / ZB
Secure the stainless steel hooks supplied in such a way on the tank cover that the
AQUA
max
®
is positioned as far as possible centrally in the tank. See to it that the pipeline
outlets for sludge and clarified water are approximately pointing in the direction of the
appropriate inflow and outflow pipelines. Connect the outlet hose (25 mm) with the
AQUA
max
®
by means of a coupler connection.
Now suspend the AQUA
max
®
on the chains supplied so that the float switch-off point agrees with
H
W,min
. The slope of the tensioned chain should not be more than 45° to the vertical
.