Installation
900921-00E, 06/2019
Innovative Hearth Products
Aries™ -C Series Direct-Vent Gas Fireplaces
41
Access the Control Compartment
See
Page 54
for instructions on
Accessing the Control Compartment
.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are
used in propane applications). Optionally, seal around the gas line to prevent cold air leakage. Gas line holes and
other openings can be caulked or stuffed with unfaced fiberglass insulation.
All codes require a shutoff valve mounted in the supply line. The orientation of the shutoff valve should face the
front.
Figure 31
illustrates two methods for connecting the gas supply. A sediment trap is recommended to prevent
moisture and debris in the gas line from damaging the valve.
Test Factory and Field Connections for Gas Leaks
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks, using a gas leak test solution—also known as bubble leak solution.
NOTE:
Using a soapy water solution is an effective leak test solution but it is not recommended, because the soap
residue that is left on the pipes/fittings can result in corrosion over time.
1.
Light the fireplace (refer to the lighting instructions label in the control compartment or
Pages 71-72
)
.
2.
Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas
odor is detected, turn the gas control knob (OFF/PILOT/ON) to the OFF position (millivolt units). Either tighten or
refasten the leaking connection, and then retest as described above.
3.
When the gas lines are tested and leak free, rinse off the leak testing solution.