background image

Installation 

900921-00E, 06/2019 

Innovative Hearth Products
Aries™ -C Series Direct-Vent Gas Fireplaces

27

Vertical (Offset) Installation

1.  Analyze the vent route and determine the number of vent sections and elbows required

—See 

Effective Vent 

Length on 

Pages 24-25

 for more information. Plan the venting so that a joint does not occur in the ceiling or 

roof joists. Allow for elbows 

(

Figure 17, Page 24

)

. Maintain clearances to combustibles equal to or greater than 

minimum specified in these instructions. 

2.  Frame the ceiling opening

—Use a plumb line from the ceiling above the fireplace to locate the center of the 

vertical run. Cut and/or frame an opening, 10-1/2 x 10-1/2” (267 x 267 mm) inside dimensions, about this center 

mark 

(

Figure 19

)

.

Figure 19 - Framing the ceiling opening

minimum 10 1/2 in.

                (267 mm)

minimum 10 1/2 in.

               (267 mm)

Roof 

Framing

Ceiling 

Framing

Plumb Bob

10-1/2” (267 mm) minimum

10-1/2” (267 mm)

minimum

3.  Attach the vent components to the fireplace

—See 

Connecting the vent pipe on 

Page 24

.

4.  Attach the vent components to each other

—See 

Connecting the vent pipe on 

Page 24

.

5.  Install firestop/spacer at ceiling

—When using Secure Vent

®

, use SV4.5VF firestop/spacer at ceiling joists; when 

using Secure Flex

®

, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/

spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer 

must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the 

firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1” (26 mm) clearance to combustibles, framing members, and attic or ceiling insulation 

when running vertical chimney sections. The gap between the vent pipe and a vertical firestop can be sealed with 

non-combustible caulking.

NOTE: Attic Insulation Shield (H3907)

 must be installed when blown or loose-fill insulation is used, and is 

required for all attic installations.

6.  Support the vertical vent run sections

—Support the vertical portion of the venting system every 8 ft (2.4 m) 

above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional 

plumber’s tape). Secure the plumber’s tape to the framing members with nails or screws. Loop the tape around 

the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2” length may be 

used to secure the support straps to the vent pipe 

(

Figure 20

)

.

NOTE: 

Proper venting support is very important.

Figure 20 - Supporting the Vertical Vent Run

Blocking

Support straps 

(plumber’s tape)

8 ft (2.4 m) 

maximum

1/2” (13 mm) 

minimum 

clearance to 

combustibles

Summary of Contents for Aries C Series

Page 1: ...ivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d...

Page 2: ...c ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personnes risques incluse avec le Facade Requis Vea e...

Page 3: ...i se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el...

Page 4: ...mum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 Construct the Fireplace Framing 17 Prepare the Fireplace Top Spac...

Page 5: ...subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un...

Page 6: ...angerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxid...

Page 7: ...e accessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have an...

Page 8: ...fois l an par la suite Des nettoyages plus fr quents peuvent tre n cessaires si les tapis la literie et cetera produisent une quantit importante de pous si re Il est essentiel que les compartiments ab...

Page 9: ...utlet side of the valve Figure 1 Figure 1 Millivolt Gas Valve Propane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pr...

Page 10: ...1372 m Model Natural Gas drill size Propane drill size 35 Models 48 0 076 Cat No J7910 56 0 046 Cat No 62L37 40 Models 45 0 082 Cat No 39L66 55 0 052 Cat No 19L52 45 Models 44 0 086 Cat No 60J80 55 0...

Page 11: ...monoxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimu...

Page 12: ...use of the fireplace are primary concerns However vent system routing to the exterior and access to the fuel supply are also important Due to high temperatures the fireplace should be located out of t...

Page 13: ...22 m 12 12 to 14 12 5 0 ft 1 52 m 14 12 to 16 12 6 0 ft 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum...

Page 14: ...to nonmechanical air supply inlet to building or the combustion air inlet to any other fireplace 6 150 mm for fireplaces 10 000 Btu h 3 kW 9 230 mm for fireplaces 10 000 Btu h 3 kW and 50 000 Btu h 15...

Page 15: ...y hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the...

Page 16: ...projections such as shelves window sills mantels etc above the fireplace NOTE To avoid heat related finish damage we recommend the use of high temperature paint rated 175 F or higher on the underside...

Page 17: ...Line Page 40 13 Verify Proper Fireplace Operation Page 41 Remote Control 14 Initialize the Remote Control System for the First Time Page 42 Finishing 15 Optional Accessory see Page 67 for ordering inf...

Page 18: ...nimum height of rear vent installations Minimum opening size additional 1 8 per side is recommended NOTE Framing specifications do NOT apply for flexible venting When using flexible venting refer to t...

Page 19: ...line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition C...

Page 20: ...the vent pipe If you require a rear vented unit remove the round outer rear flue cover 2 screws Figure 9A and the inner rear flue cover plate 4 screws Figure 9B If you require a top vented unit remove...

Page 21: ...e fireplace to the side framing members using the unit s nailing flanges one top and bottom on each side of the fireplace front Figure 10 Use 8d nails or the equivalent 3 A flush mount mounting kit is...

Page 22: ...run inside an enclosed wall There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe Figure 11B Figure 11C Figure 11D 2 Place Top trim piece and hoo...

Page 23: ...ations When vertically terminating the vent system through the roof and using the vent restrictor install the vent restrictor in the top vent of the fireplace outlet If installing more than 6 ft of ve...

Page 24: ...pic vent section SV4 5LA may be used to provide the installer with an option to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesira...

Page 25: ...3 465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0...

Page 26: ...figures Secure Flex pipe may also be used A table summarizes each configuration s minimum and maximum vertical and horizontal length parameters for a variety of applications 1 Refer to Figure 23 and T...

Page 27: ...here is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the to...

Page 28: ...al the top and both sides of the flashing with waterproof caulking The flashing must overlap the roofing material along the bottom 11 Install the storm collar Install the storm collar supplied with th...

Page 29: ...RNING Do NOT join separate sections of concentric flexible vent pipe Figure 23 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling fire...

Page 30: ...H Ceiling firestop spacer SV4 5VF H1 H 8 ft 2 4 m maximum H H1 20 ft 6 1 m maximum V V1 H H1 60 ft 18 3 m maximum Install the U shaped vent restrictor in any vent run with more than 6 ft of vertical...

Page 31: ...d determine the number of vent sections and elbows required See Effective Vent Length on Pages 24 25 for more information Plan the venting so that a joint does not occur in the ceiling or roof joists...

Page 32: ...Attach the termination adaptor Attach the adaptor SV4 5RCH provided with the termination to the vent section or telescoping vent section elbow or fireplace collar Figure 25 12 Install the firestop spa...

Page 33: ...e caulked with mill base caulk such as 10K81 or high temperature silicone Figure 26 Venting Connection and Exterior Wall Recessing of the Horizontal Termination Use silicone caulking to seal the top a...

Page 34: ...ng SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible wall WARNING Do not join separate sections of concentric flexible vent together...

Page 35: ...will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 25 ft 7 62 m NOTE The compact termination...

Page 36: ...wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 H2 Table 27 Top Vent Three 90 Elbows H Maximum V Minimum feet meters feet meters 5 1 524 Elbow only 5 1...

Page 37: ...e inner and outer adaptor collars NOTE Outer vent pipe is pulled away to show inner vent pipe details Adaptor SV4 5RF Attach adaptor to vent collar or Secure Vent sections 1 3 4 44 mm flexible vent an...

Page 38: ...or Secure Vent adaptor for Secure Flex components Secure Flex termination and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube to impr...

Page 39: ...29 Wiring Diagram Millivolt Gas Valves 1 If installing an ON OFF wall switch or thermostat mount it in a convenient location on a wall near the fireplace 2 Wire the control switch within the millivol...

Page 40: ...ine from damaging the valve NOTE Secure all joints tightly using appropriate tools and sealing compounds ensure propane resistant compounds are used in propane applications Seal around the gas line to...

Page 41: ...ure and debris in the gas line from damaging the valve Test Factory and Field Connections for Gas Leaks WARNING Never use an open flame to check for leaks Turn on gas supply and test for gas leaks usi...

Page 42: ...ng Inspect the pilot flame carefully remove logs if necessary Millivolt Fireplace Inspection The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orang...

Page 43: ...ening may need to be adjusted If the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long orange flames Sooting results in...

Page 44: ...tion by pulling rod down especially on LP gas 1 Move the adjustment rod down to increase air flow and up to decrease it The rod is located in the lower control compartment Position the air shutter to...

Page 45: ...irely flat It is suggested that the center screw should be installed first and the ends last 1 Attach hood using three screws as shown here WARNING Reinstall any barrier removed before operating the f...

Page 46: ...l Be sure the screen is turned to be flush with the front of the facade as shown in Figure 36B Top Shoulder Screws 1 ea side Bottom Shoulder Screws 1 ea side Mesh Barrier facade with barrier Mesh Barr...

Page 47: ...raftsman Artisan and Reflection See Figure 36C through 36E If the screen mesh barrier gets damaged it shall be replaced prior to operation of the fireplace Instructions will vary slightly depending on...

Page 48: ...uile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r s...

Page 49: ...mes packaged with a storm collar 77L78 SV4 5F Flat Roof Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4 5SC6 Storm Collar 6 pack H6183...

Page 50: ...or flex with 12 305 mm of compressed flex vent see 750204M 94L05 SFKIT18SS Small Square Termination for flex with 18 457 mm of compressed flex vent see 750204M 94L06 SFKIT24SS Small Square Termination...

Page 51: ...lessures ou la mort Le tecnicien agr est responsable de l installation de cette trousse L installation n est pas ad quate ni compl te tant que le bon fonctionnement de l appareil converti n a pas t v...

Page 52: ...ed by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or o...

Page 53: ...ptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chime...

Page 54: ...Figure 38A 1 2 Lift up slowly until the bottom pulls away from fireplace The facade should freely swing out toward you allowing access to the control compartment See Figure 38A 2 If you wish to remov...

Page 55: ...you local distributor or dealer Readthisinstructionsheetinitsentiretybeforebeginningtheinstallation ALL WARNINGS AND PRECAUTIONS IN THE INSTALLATION AND OPERA TION MANUAL PROVIDED WITH THE APPLIANCE A...

Page 56: ...Direct Vent Gas Fireplaces 56 Figure 39D Figure 39E Showing Lintel Figure 39C Insert Bent Bracket Bracket Insert Top Leg Of Bracket Between Lintel And Top Panel Example of Pre Bent Bracket Before Inse...

Page 57: ...n incomplete combustion sooting and poor flame quality Logs get very hot and remain hot for up to one hour after the gas supply is turned OFF Handle the logs only when cool This appliance is not desig...

Page 58: ...Rear Log 5 Twig Log 1 If necessary remove the glass door Pages 62 63 Locate the placement tabs Figure 40 2 Bend up the log placement tabs Figure 40 3 Install the rear left log 1 Figure 41 Figure 40 L...

Page 59: ...eries Log Set continued Figure 44 Place right rear log 4 Figure 45 Place twig log 5 Bottom View Top View 4 Slot fit over Tab shown in Figure 40 5 8 Tear the glowing embers into dime size pieces Place...

Page 60: ...t Bottom Log 3 Right Front Bottom Log 4 Right Rear Log 5 Twig Log 1 If necessary remove the glass door Pages 62 63 Locate the placement tabs Figure 47 2 Bend up the log placement tabs Figure 47 3 Inst...

Page 61: ...nued Figure 52 Place right rear log 4 Figure 51 Place twig log 5 8 Tear the glowing embers into dime size pieces Place glowing embers as shown in Figure 53 Figure 53 Place glowing embers rockwool NOTE...

Page 62: ...installed AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass fron...

Page 63: ...or 1 If necessary remove the door and place it in a safe location for later reinstallation 2 Remove the facade Place the facade in a safe location for later reinstallation 3 Detach the two 2 door latc...

Page 64: ...nting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodically...

Page 65: ...paint brush Reinstalling the embers and logs Carefully follow the placement instructions Pages 57 61 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame...

Page 66: ...r signs of blockage or obstruction Look for any signs of dislocation of the vent components Appliance Inspection Qualified Service Technician Perform the appropriate appliance inspection procedure det...

Page 67: ...odel Description H5820 4 5HTSK Termination Shroud 87L02 SV4 5HGS Termination Guard Deluxe 17M52 SV4 5HGS 1 Termination Guard Square Cat No Model Description 80L84 FBK 100 Blower Standard single speed...

Page 68: ...operation Large LCD screen to display room and set temperature in F and C Connects to wall switch wire Manual or up to 3 hr Countdown Timer modes LCD display Displays room temp in F or C Flame icon an...

Page 69: ...to control the operation of the fireplace burner or blower Install the OFF ON wall switch in a convenient location near the fireplace Variable Speed Wall Switch Kit The variable speed wall switch kit...

Page 70: ...eflection Warm Chestnut 40 Trad F3577 FCBK40T Facade Craftsman Black 40 Trad F3580 FCWC40T Facade Craftsman Warm Chestnut 40 Trad F3583 FABKAI40T Facade Artisan Charcoal Aged Iron 40 Trad F3569 FCFBK4...

Page 71: ...when released stop and immediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas contr...

Page 72: ...fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien qualifi ou le fournisseur de gaz 10 To...

Page 73: ...lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the...

Page 74: ...p flue MV LP takes facade F3750 ARIES40RMN C Aries 40 rear flue MV N takes facade F3751 ARIES40RMP C Aries 40 rear flue MV LP takes facade WARNING AVERTISSEMENT Never use substitute materials Use of n...

Page 75: ...lt Liquid Propane 88J53 1 88J53 1 7 Traditional Burner Assembly F3829 1 F3830 1 Vent Restrictor Base H8987 1 H8987 1 Vent Restrictor Wing H8988 1 H8988 1 Door Latch Assembly H1264 2 H1264 2 Assembly H...

Page 76: ..._________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _________________________...

Page 77: ...fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal...

Page 78: ...Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specifications pri...

Reviews: