Section 5.  Operation

5.1 

Normal Operation

The Viron XT Series 2 Pumps has three (3) pre-set 

speed settings: Low, Medium and High. 

•  Low speed is the recommended setting for everyday 

pool filtration when a cleaner is not connected.

•  Medium speed can be used for gentle spa jet action, 

when a suction cleaner is connected to the skimmer or 

pool filtration.

•  High speed should be used when backwashing, 

manually vacuuming the pool, or operating spa jets or 

some water features such as waterfalls.

5.2 

Starting Up the Pump

  CAUTION

Never run the pump without water. Running the 

pump “dry” for any length of time can cause severe 

damage to both the pump and motor and will void 

the warranty.

If this is a new pool installation, make sure all piping 

is clear of construction debris and has been properly 

pressure tested. The filter should be checked for 

proper installation, verifying that all connections and 

clamps are secure according to the manufacturer’s 

recommendations.

  WARNING

To avoid risk of property damage, severe personal 

injury or death, verify that all power is turned off 

before starting this procedure.

1. 

Depending on the location of the pump, do one of the 

following:

• 

If the pump is located below the water level of the 

pool, open the filter pressure release valve to prime 

the pump with water.

• 

If the pump is located above the water level of the 

pool, remove the lid and fill the basket with water 

before starting the pump.

2. 

Prior to replacing the lid, check for debris around 

the lid o-ring seat. Debris around the lid o-ring seat 

will cause air to leak into the system and will make it 

difficult to prime the pump. 

3. 

Hand-tighten the lid to make an air tight seal. Do not 

use any tools to tighten the lid: hand-tighten only. 

Make sure all valves are open and the unions are tight. 

Restore power to the pump. 

4. 

Once all the air has left the filter, close the pressure 

release valve.

5. 

Press the MENU button for initial programming to 

enter overdrive speed. FAST and two (2) rotating 

circles will show on the user interface display. 

• 

Viron XT Series 2 Pump primes 30% faster than 

conventional maximum speed.

• 

Viron XT Series 2 Pump automatically limits 

maximum speed according to the system’s total 

dynamic head and power consumption.

• 

Once the pump is primed (or fail to prime within 

five (5) minutes), the speed will return to the last 

speed when in the MANUAL mode. 

6. 

If the water flow is not available within 1/2-minute, 

turn off the power and prime the pump again.  After 

three (3) attempts at priming, turn off the pump and 

check for leaks.

NOTE

  If no leaks are evident, a check valve or foot valve is 

required to hold water for priming.

7. 

If water flow is not adequate after cleaning the lint 

basket, turn off the power and check for other issues 

such as the check valve, air leaks, faulty seal, cracked 

lint pot lid, etc.

8. 

The Viron XT Series 2 Pump will automatically start on 

PRIME speed for the first five (5) minutes to assist with 

priming, which will quickly fill the hair and lint pot 

with water. 

After five (5) minutes, the speed will return to the last 

speed when in the MANUAL mode. Note: See Section 

6 for further details on adjusting the Prime speed and 

Prime time.

9. 

During normal operation, it is recommended that the 

Viron XT Series 2 Pump operate on LOW speed for 

twelve (12) hours per day. This setting provides the 

lowest operating cost with the lowest noise levels. 

Should the pool have areas where the water does not 

turn over with this setting, increase the speed until the 

desired water movement is obtained.

For technical assistance, call AstralPool Technical 

Support at 1300 186 875.

5.3 

Pump Lid Removal

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the 

variable-speed pump electrical circuit before starting the 

procedure. Failure to comply may cause a shock hazard 

resulting in severe personal injury or death.

1. 

Make sure that the pump is turned OFF.

2. 

Make sure that the switch to the circuit breaker to the 

motor is turned OFF.

3. 

Make sure all necessary isolation valves are closed to 

prevent water from reaching the pump.

4. 

Following the markings on the locking ring, turn the 

ring counter-clockwise until the ‘START’ markings align 

with the ports. See Figures 11.

5. 

Carefully remove the lid with locking ring.

Summary of Contents for P320 XT P520 XT

Page 1: ...standards and any other local applicable regulations Before installing this product read and follow all warning notices and instructions that accompany this product Failure to follow warning notices...

Page 2: ...R MODEL CONTROL PANEL MODEL SERIAL NUMBER NOTES For full warranty terms and conditions and to register your warranty simply visit www astralpool com au warranty and complete your details Or scan the Q...

Page 3: ...1 Normal Operation 14 5 2 Starting Up the Pump 14 5 3 Pump Lid Removal 14 5 4 Conduct Pressure Test 15 Section 6 Viron XT Series 2 Pump Controls 16 6 1 Viron XT Series 2 Pump Control Panel 16 6 2 Spee...

Page 4: ...ceptable standard WARNING To reduce the risk of property damage or injury do not attempt to change the backwash multiport slide or full flow valve position with the pump running WARNING AstralPool Pum...

Page 5: ...e pump dry for any length of time will cause severe damage and will void the warranty WARNING To minimize risk of severe injury or death the filter and or pump should not be subjected to the piping sy...

Page 6: ...3 feet apart centre to centre See Figure 1 The system must be built to include at least two 2 suction outlets drains connected to the pump whenever the pump is running However if two 2 suction outlet...

Page 7: ...rate for your pool In addition special applications such as in floor cleaning or programming water features are enabled using the time clock and speed selection for different times of day The P520XT...

Page 8: ...iption Quantity 1 Viron XT Series 2 Pump 1 2 50 mm Union Nut 2 3 50mm Universal Union Tail 2 4 50mm Universal Union O ring 2 Table 1 XT Pump Parts 3 2 Technical Specifications Power P320XT 85 Kw outpu...

Page 9: ...ive feet horizontally from the edge of the pool and or spa Choose a location that will minimize turns in the piping 2 Place the pump on a solid foundation that will not vibrate To further reduce the p...

Page 10: ...from only one main drain At least two main drains must be connected to the pump when it is in operation However if two main drains run into a single suction line the single suction line may be equipp...

Page 11: ...IF USING A DIFFERENT BRAND HEATER All pool suction outlets and plumbing must be properly installed in compliance with applicable entrapment protection standards such as AS2610 2 Listed certified to t...

Page 12: ...e not to exceed 45 degrees 7 Pumps must be either supplied by an isolating transformer or supplied through a residual current device RCD with a rated residual operating current not exceeding 30mA 4 4...

Page 13: ...d by these devices The Viron P320XT and P520XT must have its in built timer deactivated if the pump operating times and speeds are to be operated by the compatible AstralPool Salt Chlorinator EQ RolaC...

Page 14: ...the user interface display Viron XT Series 2 Pump primes 30 faster than conventional maximum speed Viron XT Series 2 Pump automatically limits maximum speed according to the system s total dynamic hea...

Page 15: ...in death serious injury or property damage Be sure all air is properly purged out of the system before operating DO NOT USE COMPRESSED AIR TO PRESSURE TEST OR CHECK FOR LEAKS WARNING ELECTRICAL SHOCK...

Page 16: ...special purpose flow rates may include but are not limited to operating spa jets operating water falls or water features operating a suction pool cleaner High Speed is generally set up to backwash you...

Page 17: ...gain to set minutes and then press enter again to set AM or PM 5 Press Auto Power button to accept 6 The LCD screen will quickly flash 3 times to indicate the new setting has been accepted 6 3 3 Setti...

Page 18: ...d above normal high speed We recommend high speeds for Priming 4 PRIMING TIME will now appear on the screen Prime period is defaulted to 5 minutes and high speed Use the up and down arrows to change t...

Page 19: ...ods deactivated Pump speed can be changed from pump or controller 240V Power 24V Communication Data VX Salt Chlorinator TIMER CLOCK DAY Chlorine Output Set Point Decrease SAFETY BACKWASH POOL MODE SPA...

Page 20: ...16 Viron XT Series 2 Pump with RJ12 Cable Connection Viron XT Series 2 Pump is connected to Viron Heater or Other Compatible AstralPool Heater via RJ12 cable Viron Heater Status Viron XT Series 2 Pump...

Page 21: ...re release valve on the filter and make sure it is clean and ready for operation 10 Turn on the power to the pump Once all the air has been evacuated from the filter close the pressure release valve 7...

Page 22: ...n the surfaces surrounding the control to prevent ant and insect ingress Repeat every three months or as necessary Note Regular maintenance is important to ensure long life and trouble free performanc...

Page 23: ...nter season or other scheduling conflicts Check for debris build up in the skimmer basket This can cause reduced flow to the pump Also ensure that any suction cleaners are disconnected as this can be...

Page 24: ...24 viron xt series 2 pumps Installation Manual Section 9 Spare Parts 9 1 Series 2 Model P320XT and P520XT 1 2 9 10 11 12 13 8 14 3 5 7 21 22 17 18 16 19 23 20 15 4 6...

Page 25: ...NG SEAL PLATE 70030 1 1 13 SEAL PLATE SP40030 1 1 14 SEAL PLATE TO WET END BOLTS 40175 6 6 15 MOTOR RETAINING BOLT 40173 4 4 15 M8 HEX BRASS NUT 40272 6 6 16 MOTOR FOOT 4005002 1 1 16 MOTOR FOOT RUBBE...

Page 26: ...TOP TIME TIMER 4 START TIME TIMER 4 STOP TIME CURRENT TIME LOW MED HIGH TIMER 2 LOW SPEED TIMER 2 MED SPEED TIMER 2 HIGH SPEED LOW MED HIGH TIMER 3 LOW SPEED TIMER 3 MED SPEED TIMER 3 HIGH SPEED LOW M...

Page 27: ...ow Rate L min Overdrive High Speed 2850 RPM Medium Speed 2000 RPM Low Speed 1325 RPM 0 100 200 300 400 500 0 0 5 0 10 0 15 0 20 0 25 0 11 2 Series 2 Model P520XT Total Head m Flow Rate L min Overdrive...

Page 28: ...2020 Fluidra S A All rights reserved This document is subject to change without notice Fluidra Group Australia 219 Woodpark Road Smithfield NSW 2164 Australia 1 300 186 875 www astralpool com au...

Reviews: