Device description
LDS70A User Manual
Page 24
ASTECH GmbH
4.9
Digital interfaces Q1, Q2
Switching outputs Q1 and Q2 show the distance information as logical
switching information. They signalize whether the preset hysteresis switching
range is exceeded or fallen short of.
Thus, they are ideally suitable for direct further processing of monitored
values such as fill level or object detection. Parameterization is done via the
serial interface.
A load resistor of > 150 Ohms/ 6 W (max. operating voltage of 30 V; max. load
current of 0.2 A) has to be switched against VDC- (GND of supply voltage).
The load current must not exceed 0.2 A.
Figure 5: Wiring of Q1, Q2
Typical resistance: 1 kOhm against VDC- (not against GND)!