65
EN
Operation
EN
Ending an alarm
1 Push the key pushbutton in the
unlock
direction.
The acoustic alarm is ended.
The green LED flashes at a ratio of 1:1. The yellow LED goes out.
The
alarm
(Fig. 6 page 52) relay is opened.
The alarm remains active.
The cause of the alarm can be queried using the key switch.
2 If not obvious, display the cause of the alarm
(“Removing the upper part of the housing”, page 48).
3 Remove the cause of the alarm, for example, close the door or pull out the
actuated EMERGENCY-OPEN switch.
When all the alarm causes have been removed, the green LED is permanently lit.
4 Lock the door:
The alarm memory is cleared
Determining the cause of the alarm
As long as an alarm has not been reset, the green LED lights up in a ratio of 1:1. As
long as the alarm has not been reset, the cause can be queried using the key
pushbutton.
1 First actuate the key switch to the left, then to the right and pay attention to
the LED signals (Tab. 9).
Key switch
Terminal Cause of alarm
Left
Right
Light signals
Red
–
internal Tampering on the terminal or control panel
Green
Green
internal Tampering with the door (*)
Green
–
internal Emergency open (it was unlocked)
Green/Yellow
–
internal Emergency open (it was locked)
Yellow
–
6
Locked return signal missing
–
Red
13 - 14
External emergency release (for exam-
ple by fire alarm system)
no display
Centrally operated release
Acknowledge
Show alarm cause
Reset
Tab. 9
Alarm criteria and
light signals
Summary of Contents for EffEff 1340-14
Page 31: ...31 DE Technische Daten ...
Page 35: ...35 DE Checkliste Prüfung vor der Erstinbetriebnahme ...
Page 67: ...67 EN Maintenance and inspection EN ...
Page 71: ...71 EN Check list Testing before initial operation EN ...
Page 74: ...74 EN ...
Page 75: ...75 EN EN ...