
54
EN
Configuration
Mode 1: Stand-alone operation – –
models 1340-14/-15
mode 2: Bus operation –
models 1340-20/-21
DIP switch S4
Function
1
ON
factory
default
Door opening time monitoring active with alarm.
OFF
No pre-alarm or alarm due to door opening time monitoring
2
ON
factory
default
Temporary release is possible with the internal key pushbut-
ton, via terminal 20 or via the external push-button
.
OFF
Temporary release is only possible by the external push-but-
ton connected to terminals 11/12.
3
ON
factory
default
Permanent release takes place immediately after actuation
OFF
Permanent release only takes place after 5 seconds of contin-
uous actuation.
4
ON
factory
default
An acoustic alarm is emitted when the external fire alarm
system is triggered.
OFF
No acoustic alarm is emitted after the external fire alarm
system is triggered
5
ON
Mode 2 –
The escape door control terminal operates as
a bus participant on the door control bus.
Models 1340-20/-21
OFF
factory
default
Mode 1 –
Escape door control terminal operates as a
stand-alone unit.
Models 1340-14/-15
Tab. 2
DIP switch S4
(Fig. 7)
top switch: ON
bottom switch: OFF
Summary of Contents for EffEff 1340-14
Page 31: ...31 DE Technische Daten ...
Page 35: ...35 DE Checkliste Prüfung vor der Erstinbetriebnahme ...
Page 67: ...67 EN Maintenance and inspection EN ...
Page 71: ...71 EN Check list Testing before initial operation EN ...
Page 74: ...74 EN ...
Page 75: ...75 EN EN ...