19
FM437 11/18
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
For installation assistance contact Corbin Russwin
1-800-543-3658 • [email protected]
MP9800 Series
Access 600 Integrated Wiegand
with and without MELR Option (Electric Latch Retraction)
Installation Instructions
Multi-Point Lock
14
Electrical Operation Check
NOTE: Once electrical wiring has been
successfully completed according to proper
application, complete following steps.
1. Turn power ON.
2. Verify LED located on reader is ON. Red or
Green depending on reader configuration
(See reader LED Configuration).
3. Present proximity credential and verify LED
and sounder activity.
4. Verify valid card read at EAC Panel.
5. Verify system operation functions; i.e., when
credential is presented to reader that door
unlocks. (Figure 27)
Feature
WT1
WT2
12 or 24VDC solenoid
lock voltage adjustable
X
X
Operates as Fail Safe or
Fail Secure
X
X
"Learn" mode allows
testing of specific cards
without programming at
the panel level
X
X
Card reader data integri-
ty is validated at test unit
X
X
Works with SE LP10
X
X
Displays detailed
Wiegand data, including
hexadecimal string and
total bits received
X
Displays measured end-
of-line resistor values
(if applicable)
X
ASSA ABLOY Wiegand Test Unit verifies installation in the field.
Test unit checks for proper wiring, card reader data integrity, lock
functionality including lock/unlock, door position status, and re-
quest-to-exit (REX) status.
In addition, this tool provides product demonstration abilities to
highlight product’s features and capabilities.
Wiegand Test Unit
Figure 27