MP9800 Series
Access 600 Integrated Wiegand
with and without MELR Option (Electric Latch Retraction)
Installation Instructions
Multi-Point Lock
FM437 11/18
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
For installation assistance contact Corbin Russwin
1-800-543-3658 • [email protected]
3
Features
All Access 600 Multi Point Locks
• UL and CUL listed for use on Fire Doors
• Multi point lock furnished for 1-3/4” doors
• Fail safe or fail secure available
• Door Position Switch (708F989) supplied for
monitoring
• 24VDC motor operated trim available
• Wire from EAC Panel to door must be
shielded with a drain terminated at EAC
Panel controller
Access 600 MP9800 Series Multi Point Lock
• Cylinder override available for MP9800 with
Auxiliary Control
4
Regulatory Specifications
Access 600 M802
Access 600 M812
12VDC / 24VDC System:
• Reader Draw= 150mA
• Actuator Draw= 400mA
(inrush / 15mA continuous)
• Total System Draw = 550mA
• Reader Draw= 125mA
• Actuator Draw= 400mA
(inrush / 15mA continuous)
• Total System Draw = 525mA
12VDC System (MELR):
• Reader Draw = 150mA
• 12VDC MELR Module Draw =
850mA
• Total System Draw = 1 Amp
• Reader Draw = 125mA
• 12VDC MELR Module Draw=
850mA
• Total System Draw = 975mA
24VDC System (MELR):
• Reader Draw = 150mA
(Reader is always 12VDC)
• 24VDC MELR Module Draw =
700mA
• Total System Draw = 850mA
• Reader Draw = 125mA
• 24VDC MELR Module Draw =
700mA
• Total System Draw = 825mA
The M802 125 kHz (proximity) version
of the Open Architecture Wiegand
Access Control platform requires a
proximity card/fob/tag presentation
to gain entry. The 125 kHz reader
operates on 12 VDC.
The M812 13.56 MHz iCLASS®
(contactless) version of Open
Architecture Wiegand Access Control
Platform requires an iCLASS card/
fob/tag presentation to gain entry. The
13.56 MHz iCLASS reader operates
on 12VDC or 24VDC.
• UL 294 Access Control Performance Ratings*:
Destructive Attack
Level I
Line Security
Level I
Endurance
Level IV
Standby Power
Level I
• ANSI/BHMA A156.25 Listed Grade 1 Compliant
• UL and CUL listed for use on Fire Doors
• This product meets the requirements of CAN/ULC-S319-05 Equipment Class I
Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), CSA 22.1,
Canadian Electrical Code (CEC), Part I, Safety Standard for Electrical Installations, local codes, and the
authorities having jurisdiction.
*For Non-ELR Configured Product