Check that float is in correct position on shaft, with 
magnet facing upwards and that filter is in place. 
DO NOT OPERATE THIS PUMP wITHOUT FILTER. 
Fit lid onto reservoir and clip firmly in place.

Comprobar que el flotador esté en posición correcta en el eje, con el imán apuntando hacia arriba 
y el filtro es colocando. NO HAGA FUNCIONAR LA BOMBA SIN EL FILTRO. Encaje la tapa en el 
depósito y sujétela firmemente en su sitio con abrazaderas.

4

Reservoir  A  must be secured flat and level under drain pan using self adhesive Velcro strips. 
RESERVOIR  A  (Inline): To connect directly to plastic fitting at end of insulated drain hose from 
drain pan use orange rubber inlet hose  4 , cut to length as required. If it is necessary to shorten the 
insulated drain hose from the drain pan you will need to use the drain hose adapter  8  to connect 
the cut end to the reservoir inlet. 

NOTE: wHEN MAKING THIS CONNECTION, THE INSULATION MUST 

BE STRIPPED BACK AT LEAST 1” AND INNER HOSE MUST BE SECURED TO THE PLASTIC NIPPLE ON THE 
DRAIN ADAPTER wITH A CLAMP OR CABLE TIE TO ENSURE IT IS FULLy wATERTIGHT.

RESERVOIR  B  (Panmount): Mount reservoir inside drain pan, flat and level on bottom and secure 
with self adhesive Velcro strips. No inlet connection is required for this application.

ENG

ENG

ES

Installation – reservoir / Instalación – depósito

1

2

3

Example of a

ducted system

Ejemplo de un

a

sistema con 

canales de air

e

a

b

Depósito  A  puede ser asegurado plano y horizontal debajo de la bandeja de desagüe utilizando las 
tiras de velcro autoadhesivas. 
DEPÓSITO  A  (En linea): Para conectar directamente en la montaje de plastico al final de la 
manguera de desagüe aislamiento del bandeja de desagüe, utilizar la manguera de entrada de 
hule, color naranja  4  y corta a la longitud como lo exige. Si entra es necesario a cortar la manguera 
aislamiento del bandeja de desagüe, usted tendra que utilizar el adaptador para la manguera de 
drenaje  8  para conectar el extremo del corte en la entrada del depósito. 

NOTA: CUANDO HAGA ESTA CONExION, EL AISLAMIENTO DEBE SER DESPOJADO DE NUEVE POR 
LO  MENOS 1” y LA MANGUERA INTERIOR DEBE SER GARANTIZADO EN PEZON DE PLASTICO EN 
EL ADAPTADOR CON UNA PINZA O UN SUJETADOR PLÁSTICO PARA ASEGURARSE DE QUE ESTA 
TOTALMENTE HERMÉTICA.

 

DEPÓSITO  B  (Montado en la bandeja): Montaje depósito dentro bandeja de desagüe, plano y 
horizontal, en el fondo y asegurarse con tiras de Velcro autoadhesivas. No se requiere conexion de 
entrada para esta aplicacion.

ES

1

2

3

Example of a

ducted system

5

Encaje el tubo respirador en la tapa del depósito,
asegurese que el tope del tubo éste sobre el maximo nivel de agua en la bandeja de desagüe.

NoTa: Tubo reSPIraDor eS crITIco Para la oPeracIÓN correcTo De la 
bomba Y PueDe eSTar lIbre De obSTruccIoNeS eN ToDo momeNTo.

ENG

ES

Fit breather tube onto reservoir lid, ensure top of tube is above maximum 
water level in drain tray.

NoTe: breaTHer Tube IS crITIcal To correcT oPeraTIoN of 
PumP aND muST remaIN free of reSTrIcTIoNS aT all TImeS.

 

1/4” i.d. vinyl tube

tubo plástico de 
1/4” de d.i. 

9

Summary of Contents for Maxi Orange

Page 1: ...s not conform in terms of color type and specifications to the original product if no longer available This warranty does not cover replacement labor or any cost claim or incident to any defect nor do...

Page 2: ...LIMENTACI N EL CTRICA Mini Orange 115V CA 0 18A 15w 60HZ 230V CA 0 11A 16w 60HZ 24V CA 0 7A 16w 60HZ Maxi Orange 115V CA 0 28A 21w 60HZ 230V CA 0 15A 21w 60HZ Cables de alarma de 3A sin voltios contac...

Page 3: ...entrada de hule color naranja 5 Manguera de conector de pl stico de 5 de longtitud y 1 4 de d i 6 Conjunto de cable de alimentaci n naranja de 6 pies 7 Tubo respirador de pl stico con 6 de longtitud...

Page 4: ...RRANTY NO HAGA FUNCIONAR LA BOMBA EN SECO OCURRIR N DA OS GRAVES QUE DEJAR N NULA LA GARANT A ES ENG We recommeND uSINg THIS PumP for No greaTer THaN 26ft HeaD No recomeNDamoS el fuNcIoNamIeNTo Sobre...

Page 5: ...INI AND MAxI ORANGE PUMPS ARE DESIGNED TO OPERATE AT EITHER 115 OR 230 VOLTS AC 60HZ wITH A TOLERANCE OF OR 10 IN BUILDINGS wIRED FOR 208 VOLTS THE 230 VOLT PUMPS SHOULD OPERATE NORMALLy PROVIDED THIS...

Page 6: ...vaporator drain pan If condensate discharge point must be lower than drainpan then 1 4 discharge hose from pump must empty into a larger diameter drain pipe at a higher level than drainpan THIS JOINT...

Page 7: ...el im n de metal en el flotador est apuntando hacia arriba Aseg rarse siempre de que el dep sito se asiente plano y horizontal Las bombas est n ideal para la mayor a de los ambientes de trabajo y vivi...

Page 8: ...ing on surface of drainpan Installation reservoir Instalaci n dep sito Select correct reservoir type A inline or B panmount 1 Insert filter into reservoir selected DO NOT OPERATE THIS PUMP wITHOUT FIL...

Page 9: ...asegurado plano y horizontal debajo de la bandeja de desag e utilizando las tiras de velcro autoadhesivas DEP SITO A En linea Para conectar directamente en la montaje de plastico al final de la mangue...

Page 10: ...RADOR DONDE LO PERMITA EL ESPACIO 2 INSIDE LINESET COVER DENTRO DE LA CUBIERTA DE TUBER A DE COBRE 3 ABOVE CEILING POR ENCIMA EL TECHO FALSO ENG ES Install pump unit in evaporator casing above ceiling...

Page 11: ...a de la bomba y asegurela con un sujetador pl stico NO LA USE UNA MANGUERA DE DESCARGA MAS GRANDE DE de d i Direccione la manguera de descarga a un drenaje appropriado MINI ORANGE MAxIMUM 26FT MINI OR...

Page 12: ...gun el diagrama pertinente y adhiera la etiqueta de advertencia en la parte delantera de la cubierta del terminales NO USE LINEAS INDEPENDIENTES DE 115 o 230 VOLTIOS PARA ALIMENTAR LA BOMBA yA QUE EST...

Page 13: ...ommunication wire L2 G 3 3 N N L 3 G neutral neutro terminal block in condenser bloque de terminales en condensador 1 amp fuse 1 amp fusible wire nut or crimp tuerca o engarce wire nut or crimp tuerca...

Page 14: ...HT TO ELIMINATE AIR IN HOSES REFER TO PREVENTION OF SIPHONING SECTION ON PAGE 6 AND TO DETAILED GUIDELINES FOR CORRECT INSTALLATION OF DISCHARGE HOSING ON LAST PAGES OF THIS MANUAL IF NECESSARy REFER...

Page 15: ...re there any restrictions in discharge hose or breather tube f Check that reservoir filter and discharge hose are free of sludge and debris Fault Pump doesn t operate at all 1 a Is power reaching the...

Page 16: ...NSTALLATION 6 INSTALL PIPE AND WIRE STRICTLY IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS DO NOT USE DISCHARGE HOSE LARGER THAN 1 4 i d 7 DO NOT OPERATE PUMP WITHOUT FILTER 8 DO NOT RUN PUMP DRY SERI...

Page 17: ...IS VITAL THAT THE INTAKE HOSE IS KEPT FULL OF WATER AT ALL TIMES SO THAT NO AIR IS PRESENT FOR THE PUMP TO DRAW IN WHEN IT STARTS OPERATING AS LONG AS THE INTAKE HOSE REMAINS FULL OF WATER EVERY TIME...

Page 18: ...hose are completely empty at which point the siphoning stops 4 As the evaporator produces more condensate the drain pan again fills up with water which flows into the reservoir Since the intake hose...

Page 19: ...gh the pump and out of the discharge hose 3 Water level in the reservoir has now receded enough to lower the float which deactivates the pump however since an air gap is included in the discharge hose...

Page 20: ...ENZAR LA INSTALACI N 6 INSTALE PONGA TUBER AS Y CABLES ESTRICTAMENTE EN CONFORMIDAD CON LAS INSTRUCCIONES DEL FABRICANTE NO LA USE UNA MANGUERA DE DESCARGA MAS GRANDE QUE de d i 7 NO HAGA FUNCIONAR LA...

Page 21: ...O DE ESA MANERA NO HABRA AIRE QUE SEA SUCCIONADO POR LA BOMBA CUANDO EST EMPIECE A OPERAR TANTO COMO LA MANGUERA DE ENTRADA PERMANEZCA LLENA DE AGUA CADA VEZ QUE LA BOMBA ARRANQUE SERA INMEDIATAMENTE...

Page 22: ...aporador produce m s conden sados la bandeja de desag e se llena de nuevo con agua la cual fluye al dep sito Al haber aire en la manguera de entrada el ciclo se repite por s solo LA PROBLEMA ES QUE CA...

Page 23: ...bomba LA MANGUERA DE ENTRADA YA ESTA LLENA CON AGUA de all que no sea succionado aire y la bomba es inmediatamente enfriada y lubricada NO SERA ESCUCHADO EL GOLPETEO LA BOMBA AHORA EST OPERANDO ENTERA...

Page 24: ...duct Lineset covers aspen Mini condensate pumps novent Locking refrigerant caps big foot AC rooftop mounting system airtec AC equipment mounting slimduct Condensate drain hose airtec products corp 124...

Reviews: