VIPEDIA-12 – Installation Guide
U-0641-0344.doc – Issue: 06 complete, approved
Page 7 of 44
power
voice alarm
system fault
fault
SELECT BACK
FAULT
ACCEPT
FAULT
CLEAR
LAMP
TEST
DEFAULT
AUDIO
MON
Indicators and Controls
Description
power
(green)
Lit if the unit is receiving DC power.
voice alarm
(red)
Lit to indicate that a voice alarm condition is present in the PA/VA system.
system fault
(yellow)
Lit to indicate that a system fault has been detected in the PA/VA system. This requires
immediate action as part(s) of the system used for emergency functions may have been
affected. A system fault will always cause the “fault” LED to be lit as well.
A system fault is triggered by a failure of any processor or memory, critical to the Voice
Alarm system, including those of the VIPEDIA-12 itself. A communication fault between
the VIPEDIA-12 and any equipment or device that has been configured at the
VIPEDIA-12 and that is critical to Voice Alarm functions will also trigger a system fault.
LED
fault
(yellow)
Lit to indicate that the unit has detected a fault.
Flashes if a fault has not yet been accepted.
W
X
The left and right arrow keys move the item selection in the direction selected, to the next
item in the menu. The selected item is indicated by [brackets] around the selection.
S
T
The up and down arrow keys toggle a selection, or increment a number, or a letter of the
alphabet when editing.
The rotary encoder acts in the same manner as these keys, and enables faster editing.
SELECT
Press after selecting an item to confirm the selection.
BACK
Press after selecting an item to cancel the selection.
If pressed repeatedly, this returns the display to the top-level menu.
DEFAULT
Press to clear previously configured text strings quickly during system configuration, or to
return fields to their default values.
FAULT ACCEPT
Accepts all current faults, steadies the flashing fault LED indication, and turns off the
audible alarm until a new fault condition occurs.
FAULT CLEAR
Clears all faults and sets all connected equipment to the “no faults” state, which also
cancels any amplifier changeovers in effect. If there are any faults present in the system,
then they are detected anew, and reported again.
AUDIO MON
Selects Audio Monitor sub-menu on the LCD display.
Key
s
LAMP TEST
Tests all indicators on the VIPEDIA-12and on all connected mainframe and amplifier
units. The sounder and the LCD display are also tested. The display shows “LAMP + LCD
+ SOUNDER TEST”, and then, solid black characters. The menu locks for the entire
duration of the test.