VIPEDIA-12 – Installation Guide
U-0641-0344.doc – Issue: 06 complete, approved
Page 36 of 44
3.2.2.5
BOA02 - Contact Outputs (1 to 12) Connections
Field Connection
Connection to VIPEDIA-12
(via CAT5 patch lead)
VIPEDIA-12’s
RJ45
Screw-in Terminal
BOA02’s
RJ45
PORT 1
to
4
②
Description Signal
Pin
Pin
Pin
Open-collector output 1 [7]
Contact 1 [7]
1
1
1
Open-collector output 2 [8]
Contact 2 [8]
2
2
2
Open-collector output 3 [9]
Contact 3 [9]
3
3
3
Open-collector output 4 [10]
Contact 4 [10]
4 6
6
Open-collector output 5 [11]
Contact 5 [11]
5 4
4
Open-collector output 6 [12]
Contact 6 [12]
6 5
5
+ve supply (as 18V-40 V power supply
input) for open-collector outputs
+Supply 7
7
7
To/From
external
device
+ve supply (as 18V-40 V power supply
input) for open-collector outputs
+Supply 8
8
8
Open-collector output:
•
Numbers without brackets refer to CONTACTS OUT 1-6 connector
•
Numbers within brackets refer to CONTACTS OUT 7-12 connector
3.2.2.6
BOA02 - Fault/Voice Alarm Relay and BMB01 Connections
Field Connection
Connection to VIPEDIA-12
(via CAT5 patch lead)
VIPEDIA-12’s
RJ45
Screw-in Terminal
BOA02’s
RJ45
PORT 1
to
4
⑩
Description Signal
Pin
Pin
Pin
Fault relay N/C contact
Relay 1 N/C
1
1
1
Fault relay COM contact
Relay 1 COM
2
2
2
Fault relay N/O contact
Relay 1 N/O
3
3
3
Voice Alarm relay N/C contact
Relay 2 N/C
4 6
6
Voice Alarm relay COM contact
Relay 2 COM
5 4
4
Voice Alarm relay N/O contact
Relay 2 N/O
6 5
5
BMB control data / EIA RS485 9600
baud (Data+)
BMB DXP
7
7
7
To/From
external
device
As above but Data-
BMB DXN
8
8
8