VIPEDIA-12 – Installation Guide
U-0641-0344.doc – Issue: 06 complete, approved
Page 29 of 44
3.2.1.6
BOA01 - Fault/Voice Alarm Relay and BMB01 Connections
Field Connection
Screw-in Terminal
①
Connection to VIPEDIA-12
(via CAT5 patch lead)
Description Signal
Pin
+V supply input (18 – 40 V) / 500 mA
24 V
1
+V supply input (18 – 40 V) / 500 mA
24 V
2
From
external
power supply
0 V supply
0 V
3
Not applicable
(Connected to screw-in terminal
③
via the PCB.)
VIPEDIA-12’s
RJ45
Screw-in Terminal
②
BOA01’s
RJ45
④
⑩
Description Signal
Pin
Pin
Pin
Fault relay N/C contact
Relay 1 N/C
1
1
1
Fault relay COM contact
Relay 1 COM
2
2
2
Fault relay N/O contact
Relay 1 N/O
3
3
3
Voice Alarm relay N/C contact
Relay 2 N/C
4 6
6
Voice Alarm relay COM contact
Relay 2 COM
5 4
4
Voice Alarm relay N/O contact
Relay 2 N/O
6 5
5
BMB control data / EIA RS485 9600
baud (Data+)
BMB DXP
7
7
7
As above but Data-
BMB DXN
8
8
8
Screw-in Terminal
③
Description Signal
Pin
Cable screen
SCREEN
1
DC supply output (18 – 40 V)
2
Cable screen
SCREEN
3
DC supply output (0 V)
0V
4
Cable screen
SCREEN
5
DC supply output (18 – 40 V)
6
Cable screen
SCREEN
7
To/From
external
device
DC supply output (0 V)
0V
8
Not applicable
An external DC power supply (18 – 40 V) must be connected to screw-in terminal
①
if the external device (BMB01)
is to be powered from the screw-in terminal block
③
.