The following connections are possible.
1 phase, 1 neutral conductor (220–240 V~, 50-60 Hz).
To reach the rated maximum power a fuse of 48A is needed.
Install a jumper between terminals 1 and 2, between terminals 2 and 3
and between terminals 4 and 5.
2 phases, 1 neutral conductor (380–415 V 2N~, 50-60 Hz).
To reach the rated maximum power two fuses of 32A are needed.
Install a jumper between terminals 2 and 3 and between terminals 4
and 5.
3 phases, 1 neutral conductor (380–415 V 3N ~, 50-60 Hz).
To reach the rated maximum power three fuses of 16A are needed.
Install a jumper between terminals 4 and 5.
Current limiter
See chapter Settings, under parameter Con - Current limiter to set the parameter. This parameter
must be set before any pan is placed on the hob or cooking zone activated
WARNING!
Current limiter setting must be set according to your connection and circuit breakers by a
registered and qualified installer. Please read the safety regulations and the installation instructions
carefully.
WARNING!
Setting a lower value of the Current limiter parameter may cause a reduced performance of the
induction hob.
17