12.10. ALARM STAGE 2
>70 °C
1
2
3
if connected
4
5
6
7
•
Actions
Immediate visual inspection of the system by
technical personnel (e.g. fi re brigade).
Subsequently, initiation of necessary actions.
See 8.2
for the transport of the cabinets out of the building.
NOTE:
After the fi re suppression device has been triggered, the safety cabinet must be subjected to a thorough
inspection so that both fi re protection and CE conformity are maintained. For this purpose, the cabinet
must be handed over to the main factory of asecos GmbH in Gründau, where the specialist department -
depending on the degree of damage - will make an assessment of the economic effi ciency and technical
possibilities of a repair. The customer then receives an off er of either a repair or a replacement, which can
be handed over to the responsible property insurer.