24
EN
14. IO90.195.060.L8.WDC
14.1. CONNECTION TO THE POWER SUPPLY
Connections on the headpiece:
1
2
Mains plug connector
Potential-free switch
contact
Connection to the power
supply
1
2
230 V
3
14.2. ERROR AND ALARM OVERVIEW
EVENT
LED GREEN
LED RED
ACOUSTIC
ALARM
LED ON THE
COMPARTMENT
GREEN/RED
ACTIONS
Self-test error / system
error
off
turned on
5 signal tones
off
1.) Restart with RESET
button if error persists:
2.) Contact Service
Operational readiness
turned on
off
off
lights up “green”
Power failure
Flashes every 20
seconds
off
3 short signal
tones every 60
seconds
off
Check power supply
Service interval reached
LED flashes (0.5 s
on, 0.5 s off)
off
off
lights up “green”
Contact Service
Warning message:
Temperature in the
cabinet >50 °C
off
turned on
Tone interval
(every 2 seconds
for 250 ms)
lights up “green”
• Immediate inspection
of the system by
in-house qualified
personnel
• Initiation of necessary
measures
• If the internal temper-
ature falls below 50 °C,
the system returns to
normal operation and
the optical and acoustic
signals are switched off.
Alarm 1:
Temperature in a
compartment >60 °C
off
turned on
Tone interval
(every 2 seconds
for 250 ms)
ON, LED flashes
“red” (250 ms on,
250 ms off)
Evacuation of the
compartment or entire
cabinet
• The visual alarm is not time-limited.
• The acoustic alarm can be switched off using the button. However, the acoustic alarm is switched on again
after 2 minutes if the event is still present.
• If the event is no longer present, the acoustic and visual alarm is switched off.
• If the alarm I (temperature in a compartment too high) was triggered, the monitoring electronics are blocked.
The relays remain switched off, so that it is no longer possible to charge batteries in the cabinet.
• A reset can be carried out by pressing the button for longer (longer than 5 seconds) or by interrupting the
mains voltage and restarting the system. However, it only works if the temperature in the compartment is
below 60 ° C again.
Summary of Contents for IO90.078.059.057.U9.S