AC15QTP And AC20QTP Operations Manual....
31
6.3
AUTO-RESTART FEATURE
The Auto-Restart feature will safely and automatically bring the shore power converter back on-
line following a power failure and recovery event. Highlights include:
Automatically routes power from the dock to the ship’s power buss.
Front panel controls allow auto-restart to be enabled or disabled.
Auto-Restart status displayed on the LCD STATUS screen.
Fault tolerant to guarantee safe operation.
Valid shore power verified prior to restart.
Handles repeated power failures without operator intervention.
LETHAL VOLTAGES ARE AUTOMATICALLY ROUTED WITHIN THE
CONVERTER WHEN (1) INPUT POWER IS PRESENT, (2) THE
DISCONNECT SWITCH IS IN THE “ON” POSITION, AND (3) AUTO-
RESTART IS ENABLED.
LETHAL VOLTAGES WILL BE AUTOMATICALLY ROUTED TO THE
CONVERTER OUTPUT AND THE OUTPUT CONTACTOR WILL
AUTOMATICALLY CLOSE
WHEN (1) INPUT POWER IS PRESENT, (2)
THE DISCONNECT SWITCH IS IN THE “ON” POSITION, AND (3)
AUTO-RESTART IS ENABLED.
NEVER REMOVE ANY PANELS OR COVERS WITHOUT SECURING
(REMOVING) SHORE POWER WHEN AUTO-RESTART IS ENABLED.
NEVER PERFORM MAINTENANCE OR SERVICE WHILE AUTO-
RESTART IS ENABLED.
NEVER ASSUME AUTO-RESTART IS DISABLED.
NEVER USER THE DISCONNECT SWITCH TO TURN THE
CONVERTER OFF WITH AUTO-RESTART ENABLED. THE
CONVERTER CANNOT DISTINGUISH BETWEEN A VALID POWER
FAILURE AND IMPROPER USE OF THE DISCONNECT SWITCH.