AC15QTP And AC20QTP Operations Manual....
32
6.3
AUTO-RESTART FEATURE, cont.
6.3.1 Operation
Auto-Restart must be enabled from the converter front panel by simultaneously pressing two
buttons. Anytime the system status is “FAILURE,” the converter will disable the Auto-Restart
feature. The converter must be ON and ONLINE before Auto-Restart may be enabled. Pressing
the SYSTEM STATUS button
(5)
will display the SUMMARY DISPLAY which will indicate
the Auto-Restart status.
CONVERTER ACTION
FRONT PANEL OPERATION
Enable Auto-Restart
CONVERTER POWER
(4)
& F1
(13)
Disable Auto-Restart
CONVERTER POWER
(4)
& F2
(13)
6.4
TURN-OFF PROCEDURE
6.4.1 Systems Not Equipped With The Seamless Transfer Option
Transfer power from the converter to the generator. This must be performed in a “break-before-
make” method, that is, at no time can the generator(s) and shore power converter be operated in
parallel.
Disable the Auto-Restart feature if enabled.
Press the CONVERTER POWER OFF
(11)
button. The Converter Power indicator LED should
change to red. If the SYSTEM STATUS
(5)
display is active, it should indicate CONVERTER:
OFFLINE. Power has now been removed from the output, but the system remains active. The
system is now in the “standby” state.
Next press the SHORE POWER OFF
(10)
button. The Converter Power indicator LED
(10A)
should change to red. This will initiate the inverter shutdown. The system will complete the
shutdown process within 10 seconds.