AC15QTP And AC20QTP Operations Manual....
45
CONVERTER OUTPUT VOLTAGE CONTROL
Vout = XXX.X
More Less XXXV Exit
EVENT LOG CONTROL SCREEN
F1: EVENT LOG VIEWER XXXX Events
F2: EVENT LOG TRACKER
F3: EVENT LOG REGISTRY
7.8
CONVERTER OUTPUT VOLTAGE CONTROL
Press the
CONVERTER POWER + F5
buttons to access the CONVERTER OUTPUT
VOLTAGE CONTROL display.
This function allows the user to increase or decrease the converter output voltage (Vout). Press
the More
(F1)
button to increase the Vout, the Less
(F2)
button to decrease the Vout, the XXXV
(F3)
button to return Vout to the factory programmed setting, and the Exit
(F5)
button to save
the setting and exit.
Default
Range
Increments
Vout
factory prog. voltage
+/-5%
0.5 volts
Application: if the line-drop losses in a yacht are such that locations remote of the converter and
Ship's Bus experience undesirable, lower-than-expected voltages, the programmed Vout can be
raised up to 5% via this function. Also, to decrease total power usage, the Vout could be reduced
up to 5%. The new, programmed Vout will be used as the basis for AGC, Seamless Transfer,
and all other voltage dependent functions.
7.9
EVENT LOG
Press the
EVENT LOG
(or
CALIBRATE
on older converters) button to access the EVENT
LOG display.
This is for monitoring internal converter logic operation. Press the
SYSTEM STATUS
button
in any screen to exit.