Ascon Tecnologic - T31- OPERATING INSTRUCTIONS - PAG. 8

7.  PROBLEMS AND MAINTENANCE

7.1 

Cleaning

It is raccomended to clean the instrument only with a cloth 
welted with water or with a detergent neither abrasive nor 
containing solvents.

7.2 

Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

8.  WARRANTY AND REPAIRS

The instrument is under warranty against construction vices 
or defected material, noticed within 18 months from delivery 
date.  The warranty is limited to the repairs or to the substitu-
tion of the instrument.  The eventual opening of the housing, 
the violation of the instrument or the wrong use and installa-
tion of the product means the automatic decay of the warranty.
In case of defected instrument, noticed in warranty period  or 
out of warranty, do contact our sales department to obtain 
the shipment authorisation.
The defected product must be shipped to Ascon Tecnologic with 
the detailed description of the failures found and without any 
fees or charge for Ascon Tecnologic, safe different agreements.

9.  TECHNICAL DATA

9.1 

Electrical data

Power supply:

 24 ÷ 240 VAC ±10%;

AC frequency:

 50/60 Hz;

Power consumption:

 About 3 VA;

Inputs: 2

 voltage 

digital inputs

 24 ÷ 240 AC/VDC;

Outputs:

 Up to 

2 relay outputs

:

EN 61810

EN 60730

UL 60730

Out1

 - SPDT - 8A -  

1/2 HP 250V

8 (3) A

10 (4) A

10 A Res.,  
12 LRA

Out2

 - SPDT - 8A -  

1/2 HP 250V

8 (3) A

10 (4) A

10 A Res.,  
12 LRA

Relay output Electrical life:

 100000 operations;

Overvoltage category:

 II;

Protection class:

 Class II;

Insulation:

 Reinforced insulation between low voltage parts 

(power supply and relay outputs) and front panel; Main insu-
lation between power supply and relay outputs; Main insula-
tion between relay outputs; No insulation between power 
supply terminals and inputs.

9.2 

Mechanical characteristics

Housing:

 Self-extinguishing plastic, UL 94 V0;

Heat and fire resistance category:

 D;

Ball Pressure Test as described in EN60730:

 accessible 

parts 75°C; support live parts 125°C;

Dimensions:

 30 x 90 mm, depth 67 mm;

Weight:

 About 120 g;

Mounting: 

Rear panel on Omega DIN rail;

Connections:

Inputs: 

Screw terminals for 0.2 ÷ 2.5 mm

2

AWG 24 ÷ 14 cables;

 

Power supply: 

crew terminals for 0.2 ÷ 2.5 mm

2

AWG 24 ÷ 14 cables;

Pollution degree:

 2;

Operating temperature:

 0 ÷ 50°C;

Operating humidity: 

< 95 RH% with no condensation;

Storage temperature:

 -25 ÷ +60°C.

9.3 

Functional features

Time range:

 4 programmable timing scales:

9999

 h,

99

 h 

59

 min,

99

 min 

59

 s,

99

 s 

99

 hundreds of second;

Input delay:

 15 ms max.;

Compliance:

Directive LV 2014/35/EU

 (EN 60730-1, EN 60730-2-7, 

EN61812-1, UL 508); 

Directive EMC 2014/30/EU

 (EN55011: class B; 

EN61000-4-2: 8 kV air, 4 kV cont.; EN61000-4-3: 10V/m; 
EN61000-4-4: 2 kV supply and relay outputs, 1 kV inputs; 
EN61000-4-5: supply 2 kV com. mode, 1 kV\diff. mode; 
EN61000-4-6: 3V).

10. HOW TO ORDER

a:  POWER SUPPLY

 

U

  =  24 ÷ 240 VAC/VDC

b:  OUTPUT 1 (OUT1)

 

S

  =  Relay SPDT 8A-AC1 (for resistive loads)

d:  TERMINALS

 

V

  =  Screw terminals (standard)

c:  OUTPUT 2 (OUT2)

 

S

  =  Relay SPDT 8A-AC1 (for resistive loads)

e, f, g

RESERVED CODES;

hh, ii

SPECIAL CODES;

MODEL

T82N

  = Timer with NFC programming interface

c

a - b

d e f g hh

ii

Summary of Contents for T82N

Page 1: ...FC communication interface embedded in the instrument The instrument offers the possibility to program up to 3 delay times or Set Times 6 operating modes for Out1 output 10 operating modes for Out2 ou...

Page 2: ...ent for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures The instrument must not be used in dangerous environ ments flammable or explos...

Page 3: ...NC NO C NC C NO Voltage inputs 24 240 VAC VDC 24 240 VAC VDC 5 OPERATING MODE 5 1 Counting commands operation Counting is enabled and disabled using the the digital inputs CNT and RST The operating mo...

Page 4: ...Reset and a new Start signal Reset OUT1 Start off f o1t 2 S t1 F o1t 3 Asymmetrical oscillator with start ON This operating mode requires the setting of both S t1 and S t2 Set times Received the Star...

Page 5: ...t f o1t 3 f o2t 3 OUT1 off off S t1 S t1 S t2 OUT2 off off S t3 S t3 Reset Start f o1t 4 f o2t 3 OUT1 off S t2 S t1 OUT2 off off off off off S t3 S t2 S t1 S t3 Reset Start f o1t 5 f o2t 3 OUT1 S t2 S...

Page 6: ...Out1 but with an S t3 interme diate settable dead time Also in this case this function is intended to be used with F o1t 3 or 4 only oscillator mode functioning in order to obtain the alternated opera...

Page 7: ...TOP 5 Bistable RESET START STOP 6 Bistable START STOP RESET 4 8 F o1t OUT1 output operating mode 1 On delay 2 Feed through 3 Asymmetrical oscillator with start ON 4 Asymmetrical oscillator with start...

Page 8: ...tput Electrical life 100000 operations Overvoltage category II Protection class Class II Insulation Reinforced insulation between low voltage parts power supply and relay outputs and front panel Main...

Reviews: