Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 44
]
Pr8 Group - Program 8
no. Param.
Description
Dec.
Point
Values
Default
380
P8.F
Program 8 - Action at power up
0
nonE
Programmer not used;
S.uP.d Start at power up with a first step in stand-by;
S.uP.S Start at power up;
u.diG
Start at Run command detection only;
u.dG.d Start at Run command with a first step in stand-by.
nonE
381
P8.u
Program 8 - Time unit of the soaks
2
hh.nn
Hours and minutes;
nn.SS Minutes and seconds.
hh.nn
382
P8.E
Program 8 - Instrument behaviour at the
end of the program execution
0
cnt Continue;
SPAt
Go to the set point selected by A.SP;
St.by
Go to stand-by mode.
A.SP
383
P8.nE
Program 8 - Number of executions
0
1... 99 times/inF indefinitely
384
P8.Et
Program 8 - Time of the end program
indication
2
0.00 (oFF)/0.01... 99.59 nn.ss/inF (steady ON)
oFF
385
P8.S1
Program 8 - Set point of the first soak
dP
From SPLL to SPHL
0
386
P8.G1
Program 8 - Gradient of the first ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
387
P8.t1
Program 8 - Time of the 1
st
soak
2
0.00... 99.59 Time unit of the soaks
0.10
388
P8.b1
Program 8 - Wait band of the 1
st
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
389
P8.E1
Program 8 - Events of the 1
st
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
390
P8.S2
Program 8 - Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
391
P8.G2
Program 8 - Gradient of the 2
nd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
392
P8.t2
Program 8 - Time of the 2
nd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
393
P8.b2
Program 8 - Wait band of the 2
nd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
394
P8.E2
Program 8 - Events of the 2
nd
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
395
P8.S3
Program 8 - Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
396
P8.G3
Program 8 - Gradient of the 3
rd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
397
P8.t3
Program 8 - Time of the 3
rd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
398
P8.b3
Program 8 - Wait band of the 3
rd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
399
P8.E3
Program 8 - Events of the 3
rd
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
400
P8.S4
Program 8 - Set point of the 4
th
soak
dP
OFF or from SPLL to SPHL
0
401
P8.G4
Program 8 - Gradient of the 4
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
402
P8.t4
Program 8 - Time of the 4
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
403
P8.b4
Program 8 - Wait band of the 4
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
404
P8.E4
Program 8 - Events of the 4
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
405
P8.S5
Program 8 - Set point of the 5
th
soak
dP
OFF or from SPLL to SPHL
0
406
P8.G5
Program 8 - Gradient of the 5
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
407
P8.t5
Program 8 - Time of the 5
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
408
P8.b5
Program 8 - Wait band of the 5
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
409
P8.E5
Program 8 - Events of the 5
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
410
P8.S6
Program 8 - Set point of the 6
th
soak
dP
OFF or from SPLL to SPHL
0
411
P8.G6
Program 8 - Gradient of the 6
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
412
P8.t6
Program 8 - Time of the 6
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
413
P8.b6
Program 8 - Wait band of the 6
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
414
P8.E6
Program 8 - Events of the 6
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00