Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 35
no. Param.
Description
Dec.
Point
Values
Default
59
HSEt
Hysteresis of the ON/OFF control dP
0... 9999 (E.U.)
1
60
Pb
Proportional band
dP
1... 9999 (E.U.)
50
61
ti
Integral time
0
0 (oFF)/1... 9999 (s)/inF (integral time excluded)
200
62
td
Derivative time
0
0 (oFF)/1... 9999 (s)
50
63
Fuoc
Fuzzy overshoot control
2
0.00... 2.00
0.50
64
tcH
Heating output cycle time
1
0.1... 130.0 (s)
20.0
65
rcG
Power ratio between heating and
cooling action
2
0.01... 99.99
1.00
66
tcc
Cooling output cycle time
1
0.1... 130.0 (s)
20.0
67
rS
Manual reset (Integral pre-load)
1
-100.0... +100.0 (%)
0.0
68
Str.t
Servomotor stroke time
0
5... 1000 (s)
60
69
db.S
Servomotor dead band
1
0.0... 10.0
0.5
70
od
Delay at power up
2
0.00 (oFF)/0.01... 99.59 (hh.mm)
oFF
71
St.P
Maximum power output used
during soft start
0
-100... 100 (%)
0
72
SSt
Soft start time
2
- 0.00 (oFF);
- 0.01... 7.59 (hh.mm);
- inF (always ON).
oFF
73
SS.tH
Threshold for soft start disabling
dP
-1999... +9999 (E.U.)
9999
]
SP group - Set point parameters
no. Param.
Description
Dec.
Point
Values
Default
74
nSP
Number of used set points
0
1... 4
1
75
SPLL
Minimum set point value
dP
From -1999 to SPHL
-1999
76
SPHL
Maximum set point value
dP
From SPLL to 9999
9999
77
SP
Set point 1
dP
From SPLL to SPLH
0
78
SP 2
Set point 2
dP
From SPLL to SPLH
0
79
SP 3
Set point 3
dP
From SPLL to SPLH
0
80
SP 4
Set point 4
dP
From SPLL to SPLH
0
81
A.SP
Selection of the active set point
0
From 1 (SP 1) to nSP
1
82
SP.rt
Remote set point type
0
RSP
The value coming from serial link is used as remote
set point;
trin
The value will be added to the local set point selected
by A.SP and the sum becomes the operative set point;
PErc
The value will be scaled on the input range and this
value will be used as remote SP.
trin
83
SPLr
Local/remote set point selection
0
Loc Local;
rEn Remote.
Loc
84
SP.u
Rate of rise for
POSITIVE
set point
change (ramp UP)
2
0.01... 99.99 Eng. units per minute/inF (ramp disabeld)
inF
85
SP.d
Rate of rise for
NEGATIVE
set point
change (ramp DOWN)
2
0.01... 99.99 Eng. units per minute/inF (ramp disabeld)
inF