Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 18
Pr.td During a soak, the instrument will show the
remaining time of the soak (count down);
• During a ramp the display will show the
operative set point;
At the end of the program execution, the
instrument shows
P.End
message alterna-
tely with the measured value;
• When no program is running, the instru-
ment will show the standard display;
P.t.tu When the programmer is running, the di-
splay shows the total elapsed time.
At the end of the program execution, the
instrument show
t.End
message alternately
with the measured value;
P.t.td When the programmer is running, the display
shows the total remaining time (count down).
At the end of the program execution, the in-
strument shows
P.End
message alternately
with the measured value;
PErc Percent of the power output used during soft
start (when the soft start time is equal to infi-
nite, the limit is ever active and it can be used
also when ON/OFF control is selected).
[90] di.CL - Display colour
Available:
Always (not available on those controllers with
white display).
Range:
0 The display colour is used to show the actual
deviation (PV - SP);
1 Display red (fix);
2 Display green (fix);
3 Display orange (fix).
[91] AdE - Deviation for display colour management
Available:
When [90] di.CL = 0 (not available on those con-
trollers with white display).
Range:
1... 9999 engineering units.
[92] diS.t - Display time out
Available:
Always.
Range:
oFF
The display is always ON;
0.1... 99.59 minutes and seconds.
Note:
This function allows to turn OFF the display when no
alarm is present and no action is made on the instrument.
When diS.t is different from OFF and no button is
pressed for more than the programmed time out, the
display goes OFF and only 4 segments of the less
significant digit are turned ON in sequence in order to
show that the instrument is working correctly.
If an alarm occurs or a button is pressed, the display
returns to the normal operation.
[93] FiLd - Filter on the displayed value
Available:
Always.
Range:
oFF
Filter disabled;
From 0.0 (oFF) to 20.0 engineering units.
Note:
This is a “window filter” related to the set point; it is applied
to the displayed value only and it have no effect on the
other functions of the instrument (control, alarms, etc.).
[95] dSPu - Instrument Status at power up
Available:
Always.
Range:
AS.Pr Starts in the same way it was prior to the
power down;
Auto
Starts in Auto mode;
oP.0
Starts in manual mode with a power output
equal to zero;
St.bY
Starts in stand-by mode.
Notes: 1.
When you change the value of [96] oPr.E, the in-
strument forces [97] oPEr parameter equal to Auto.
2.
During program execution the instrument stores
the segment currently in use and, by a 30 minutes
interval, it stores also the elapsed time of the soak.
If a power down occurs during program execution,
at the next power up the instrument is able to
continue the program execution starting from the
segment in progress at power down and, if the
segment was a soak, it is also capable to restart
from the soak time minus the stored elapsed time.
In order to obtain this features, the “[95] dSPu -
Status of the instrument at power up” parameter
must be set to “AS.Pr”.
If the “[95] dSPu” parameter is different from “AS.
Pr” the storing function is inhibited.
[96] oPr.E - Operative modes enabling
Available:
Always.
Range:
ALL
All modes will be selectable by the next
parameter.
Au.oP Auto and manual (OPLO) mode only will be
selectable by the next parameter.
Au.Sb Auto and Stand-by modes only will be se-
lectable by the next parameter.
Note:
Changing the value of [96] oPr.E, the instrument
forces [97] oPEr parameter to Auto.
[97] oPEr - Operative mode selection
Available:
Always.
Range: •
When [96] oPr.E = ALL:
Auto
Auto mode;
oPLo
Manual mode;
St.bY
Stand by mode.
• When [96] oPr.E = Au.oP:
Auto
Auto mode;
oPLo
Manual mode.
• When [96] oPr.E = Au.Sb:
Auto
Auto mode;
St.bY
Stand by mode.
]
Ser group - Serial link parameter
[98] Add - Instrument address
Available:
Always.
Range:
oFF
Serial interface not used;
1... 254.
[99] bAud - Baud rate
Available:
When [98] Add different from oFF.
Range:
1200
1200 baud;
2400
2400 baud;
9600
9600 baud;
19.2
19200 baud;
38.4
38400 baud.